Name
Digital IN (DI 1)
Digital IN (DI 2)
Bus Wilo Net
SSM
SBM
Table 9: Terminal assignment
7.6
Analog input (AI1) or (AI2) – purple terminal block
Fig. 15: Analog In
Analog signal sources connected to terminals 12 and 13 for use with AI1 and connected to terminals 22 and
23 for use with AI2
Note correct polarity for signals 0 – 10 V, 2 – 10 V, 0 – 20 mA and 4 – 20 mA.
Use the pump to supply 24 V DC to an active sensor. For this purpose, pick off the voltage at +24 V (11) and
GND I (12) terminals.
NOTICE
The 24 V DC power supply is only available when the analog input AI1 or AI2 has been con-
figured for a type of use and a signal type.
Installation and operating instructions • Wilo-Stratos MAXO/-D/-Z • Ed.02/2023-10
Assignment
DI 1 → (terminal: 33)
+ 24 V (terminal: 31)
DI 2 → (terminal: 43)
+ 24 V (terminal: 41)
↔ H (terminal: 51)
↔ L (terminal: 53)
GND H/L (terminal: 52)
COM (terminal: 75)
← FAULT (terminal: 78)
← OK (terminal: 76)
COM (terminal: 85)
← RUN (terminal: 88)
Note
Digital inputs for potential-free contacts:
• Maximum voltage: < 30 V DC / 24 V AC
• Maximum loop current: < 5 mA
• Operating voltage: 24 V DC
• Operating loop current: 2 mA per input
Potential-free changeover contact
Contact load:
• Permitted minimum: SELV 12 V AC / DC,
10 mA
• Permitted maximum: 250 V AC, 1 A,
AC 1 / 30 V DC, 1 A
Potential-free normally open contact
Contact load:
• Permitted minimum: SELV 12 V AC / DC,
10 mA
• Permitted maximum: 250 V AC, 1 A,
AC 1 / 30 V DC, 1 A