Code
Error
614
Sensor source not available.
The sensor source or the CIF module is not correctly configured. In the context menu there are
links for configuration.
615
Sensor source not suitably
configured.
The sensor source is not correctly configured. In the context menu there is a link for configuring
the sensor source.
618
Sensor source not available.
The sensor source or the CIF module is not correctly configured. In the context menu there are
links for configuration.
619
Sensor source not suitably
configured.
The sensor source is not correctly configured. In the context menu there is a link for configuring
the sensor source.
621
Sensor source not available.
The sensor source or the CIF module is not correctly configured. In the context menu there are
links for configuration.
641
Setpoint source not suitably
configured.
The setpoint source for the cooling function is not correctly configured. In the context menu
there is a link for configuring the setpoint source.
642
Setpoint source not available.
The setpoint source for the cooling function or the CIF module is not correctly configured. In the
context menu there are links for configuration.
643
Sensor source not suitably
configured.
The sensor source for the cooling function is not correctly configured. In the context menu there
is a link for configuring the sensor source.
Installation and operating instructions • Wilo-Stratos MAXO/-D/-Z • Ed.02/2023-10
Cause
Feed temperature is not
connected to existing CIF
module.
Return temperature sensor
is not connected to correct
source. Input not suitably
configured.
Return temperature is not
connected to existing CIF
module.
Temperature sensor for
"Heating/cooling
switchover" is not con-
nected to the correct
source. Input not suitably
configured.
Temperature value for
"Heating/cooling
switchover" is not con-
nected to existing CIF
module.
Setpoint is not connected
to correct source. Input not
suitably configured.
Setpoint not connected to
existing CIF module.
Sensor 1 is not connected
to correct source. Input not
suitably configured.
Remedy
Insert CIF module.
Activate CIF module.
Configure source to "temperature
sensor" usage type or select an-
other source.
Insert CIF module.
Activate CIF module.
Configure source to "temperature
sensor" usage type or select an-
other source.
Insert CIF module.
Activate CIF module.
Configure source or
select another source.
Insert CIF module.
Activate CIF module.
Configure source.
Select other source.
en-US
155