Define limit value for cable break by turning the operating button and confirm by pressing it.
In the next step define whether
•
the analog signal only changes the setpoint
•
and the pump is additionally switched off through the analog signal.
A setpoint change can be done through analog signals without switching on and off the pump through the
signals. In this case, "Switched off" is selected.
If the "On/off by analog signal" function is switched on, the limit values must be defined for the switch on/
off.
Subsequently assign the MIN signal/value and MAX signal/value.
ON/OFF through analog signal
Analog input (AI2)
Fig. 55: ON/OFF through analog signal
114
Switched off
Switched on
Installation and operating instructions • Wilo-Stratos MAXO/-D/-Z • Ed.02/2023-10
The analog signal
changes the setpoint and
switches the pump ON
or OFF
via a limit value.