13.5
Operating data/statistics
In the "Diagnostics and measured values" menu
1.
"Operating data, statistics".
The following operating data, measurement data, and statistical data are displayed:
Hydraulic operating data
Actual delivery head
Actual volume flow
Actual fluid temperature (if a temperature sensor is connected and configured)
Electrical operating data
Power voltage
Power consumption
Total energy absorbed
Operating hours
Measured heat quantity
Total heating quantity
Heat quantity since the last time the counter was re-set
Actual heating capacity
Actual feed temperature
Actual return temperature
Actual volume flow
Measured cooling quantity
Total cooling quantity
Cooling quantity since the last time the counter was re-set
Actual cooling output
Actual feed temperature
Actual return temperature
Actual volume flow
Accuracy of the displayed and recorded operating data
Volume flow:
The accuracy of the volume flow specification with pure water is approx. +/- 5% of the duty point.
If a water-glycol mixture is used, the accuracy decreases.
Temperature:
A temperature sensor is installed in the pump housing for temperature detection.
The accuracy of the temperature is +/- 0.5 K in the temperature range of 104 °F ... 176 °F (+40 °C ... +80 °C).
Outside these temperatures 14 °F ... 104 °F and 176 °F ... 230 °F (-10 °C ... +40 °C and +80 °C ... +110 °C) the
accuracy is +/- 2 K.
Heating/cooling quantity measurement:
The information on the heating and cooling quantity is derived from the recorded temperatures in the feed
and return and from the volume flow. The accuracy of the heat quantity measurement is +/- 10%, that of
the cooling quantity measurement +/- 25%.
Installation and operating instructions • Wilo-Stratos MAXO/-D/-Z • Ed.02/2023-10