• Engine Starts But Then Stalls
Check the fuel level in the tank.
Sufficient
Loosen the drain screw and check whether
fuel is reaching the carburetor.
Fuel reaching the carburetor
Check whether an error code is displayed
on the i-Monitor when stopping the engine.
Not displayed
Check whether the overload indicator is on
when stopping the engine.
Disconnect the AC appliance(s). Check
whether foreign substance is blocking the
cooling air duct causing overheating.
Check whether the generator is placed by
the side of a wall.
Check the harness connecting the inverter
unit and AC receptacle for open or short
circuit and for proper connection.
Check the harness connecting the inverter
unit and generator for open or short and for
proper connection.
Wire harness check points
GENERATOR WIRE HARNESS
GENERATOR
(MASTER)
GENERATOR
(SLAVE)
Bu: BLUE
R: RED
W: WHITE
Viewed from terminal side
Normal
Check the generator (P. 11-7).
Normal
Replace the inverter unit and retest (P. 6-2).
2-31
ON
Good
INVERTER
UNIT
Bu
W
R
INVERTER
UNIT
Bu
W
R
Insufficient
Add fuel and then restart the engine.
Not reaching
Check for restriction in the fuel filter, fuel
the carburetor
valve or fuel tube (P. 7-2).
Displayed
Refer to Failure By Error Code (P. 2-11).
OFF
Incorrect
Set the generator in the correct position and
restart the engine and recheck.
Abnormal
Replace or repair the main wire harness
and/or generator wire harness.
Abnormal
Replace the stator (P. 11-5).
To P. 2-32