cap.02 EU65is 6500is (Eu).qxd 07.12.17 4:25 PM ページ2-21
E-05
E-06
,
(GCU internal failure or inverter unit internal failure)
Check the generator (P. 11-7).
Check the main wire harness in the control box for open or
short circuit and for proper connection.
Check the harness connecting the generator and GCU for open
or short circuit and for proper connection.
Wire harness check points
GENERATOR WIRE
HARNESS
W
Bu
R
GENERATOR
(SLAVE)
Check the inverter unit (P. 6-3 and 4).
Turn the ignition switch OFF and then restart the engine and
check the error code. If the same error occurs, replace the GCU
(P. 6-6).
2-21
Normal
Normal
CONTROL WIRE
HARNESS
W
Bu
R
Viewed from terminal side
Normal
Normal
Abnormal
Abnormal
Abnormal
GCU
Bu: BLUE
R: RED
W: WHITE
Abnormal
Replace the stator (P. 11-5).
Replace or repair the main wire
harness.
Replace or repair the control wire
harness and/or generator wire
harness.
Replace the inverter unit (P. 6-2).