13.5.6

Emergency mode (Protection Mode activated)

Activation of "Protection Mode" is carried out using digital input "D2". If enabled previously during
start-up, it is activated when the contact at terminals "D2-D2" is closed.
For activation with an open contact at terminals "D2-D2" (advantage for line break), corresponding
programming in the IO setup is required (DI2 = Inverting ON).
Example of activated Protection Mode
1 The fire symbol is flashing, the output frequency is 49.9 Hz (example)
2 Constant speed is set with programming to PM specification Internal
3 Variable speed is set with programming to PM specification External
4 Mains connection with line fuse
5 Enable contact at digital input D1
6 Protection Mode activated via digital input D2 = emergency mode
7 Fan with 3 ~ motor and built-in thermostat (motor protection)
Protection Mode is activated regardless of the following settings and operating states:
Motor setting
Shut down via digital input "D1" (no enable)
Motor fault (interruption between terminals "TB/TP)"
Supply phase failure (line fault message)
L-BAL-E304-GB 2004
Factory setting
Default setting
Standard mode
Protection Mode
OFF
D1
OFF
OFF
D2
OFF
|
|
OFF
in Start menu group
Part.-No.
132/139
With Protection Mode: Digital input "D1" for
1D
device enable.
D1
OFF
DI2
With Protection Mode: Digital input "D2" for
34D
activating Protection Mode.
D2
In factory setting (Inverting = OFF), Protec-
tion Mode is active when the contact at
OFF
terminals "D2-D2" is closed.