Installation and Operating Specification FU Comfort Sinus
5.4

Mains connection

5.4.1

Line voltage

Power from the mains is connected to terminals: PE, L1, L2, L3 and N (depending on type). Here, it
must be strictly observed that the mains voltage lies within the allowable tolerance specifications (
Technical data and nameplate affixed to the side).
The neutral conductor connection "N" is only available for the device types with 22 A rated current for
the reduction of the leakage current. It is irrelevant for the device's functionality, for those supply
networks without neutral conductors the connection is not required. Because however, higher leakage
currents can flow through the "PE" conductor connection, undesirable erroneous activation may occur
on systems equipped with FI circuit breakers.
Attention!
Not suitable for IT system!
Do not operate on Grounded Delta System!
To activate the on current limitation, you must wait at least 90 seconds after switching off the line
voltage before switching back on!
5.4.2

Line protection fuse

The connection must be fused depending on the used cable, the type of routing, the operating
conditions and according to the standards applicable on site. The specification for the maximum
admissible line fuse of the device must be observed (see technical data).
Possible components for the line protection (recommendation):
Safety fuses of operating class "gG" (whole range fuse cartridges for general applications according
to EN 60269-1).
Line protection switch with characteristic "C" (according to EN 60898-1).
5.4.3

Required quality attributes for the mains voltage

Danger due to electric current
The mains voltage must comply with the EN 50160 quality characteristics and the defined standard
voltages in IEC 60038!
5.4.4
Leakage current, securely attached, ground wire double up to 10 mm²
Danger due to electric current
In accordance with the defined networks in DIN EN 60990, the device has a leakage current > 3.5 mA
so it must be permanantly connected. The protective ground must be made double in accordance with
EN 50178 Point 5.2.11and 5.3.2.1 up to a cross section of at least 10 mm².
5.5

Residual-current-operated protective device

Danger due to electric current
For an installation of r.c.d. protection, it shall be observed that this must be of "universal-current
sensitivity" (Type B). In accordance with EN 50 178, Section. 5.2. other types of current-operated
protective devices may not be used. To ensure as high a degree of reliability as possible , we
recommend a tripping current of 300 mA.
5.6

Inverter output

5.6.1

Motor connection

The motor leads are connected to the terminals: PE, U, V, W. Several fans can be connected to the
controller-the maximum total current of all motors must not exceed the current rating for the controller.
Information
It is recommended that a separate motor protection unit be foreseen for each fan.
L-BAL-E304-GB 2004
Part.-No.
16/139
Electrical installation