First Start-Up - Helios FU Comfort Sinus Manuel De Montage Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Specification FU Comfort Sinus
7.2

First Start-up

1. Before first-time start-up can take place, all the necessary components must be connected
(see Wiring Diagram Standard).
2. The device has a start-up wizard
The following parameters are prompted.
a) Language
b) MotorRatedCurr.
c) Protection Mode *
d) Mode (Modus)
e) Setpoint
f) Pband
AfterselectingLanguage,Motorratedcurrentand"Operating"mode"a"nominal"value"and then a Pband
are suggested respectively. The suggestion can be accepted in most cases. Later changes are
possible at any time after first-time start-up.
The first time the device is switched on, you go automatically to the Start-up menu. After selecting the
language, the possible mode variants are displayed first. Also see the printout in the display.
* Protection Mode
Protection mode is designed for controlling the speed of fans in safety systems. The focus is on ensuring the
longest possible operating time of components in an emergency, for example to ensure the longest possible
smoke extraction time in case of fire. Protective functions for the frequency converter and the connected fans
that can normally cause the system to shut down are deactivated for this purpose.
Proceed as follows:
"Protection Mode"
Confirm
"
"Protection Mode"
Set
"
"Mode"
the
this function.
The desired value is found using
and confirmed with
.
After setting the "language" and "mode"
the desired "nominal value "is set, fol-
lowed by the "control range".
Select respectively with the "Up" and
"Down" keys and confirm with "P".
The successful start-up is confirmed with "OK".
The device is now ready for operation. Then the control or the current actual value is displayed.
Extensive further settings can be made as required. See these instructions.
3. The first-time start-up wizard can be reactivated if desired.
To do this, press "Esc" (arrow "Up" and "Down" briefly together) until the "Start "menu is displayed.
With "P" you first go to the "PIN" selection.
Press "P" again. Now the code
the first-time start-up wizard, see section 3.
L-BAL-E304-GB 2004
|
OFF
with
|
|
ON
to
if the function is required and confirm this setting using the
chapter in the appendix for the PIN and observe the subsequent instructions for programming
or
|
|
1020
|
if the function is not required.
Modus 1.01:
Manuelle Regelung
Bereich: 0 bis 100 %
Modus 2.01:
Temperaturregelung
Bereich: -27 bis +75 °C
Modus 2.03:
Temperaturregelung mit Zusatzfunktion
Bereich: -27 bis +75 °C, 0 bis 10 Volt
Modus 2.05:
Differenztemperaturregelung
Bereich: -27 bis +75 °C
Modus 4.01:
Druckregelung
Bereich: 4 bis 500 Pa
Modus 4.02:
Druckregelung mit Außentemperaturkomp.
Bereich: 4 bis 500 Pa, -20 bis +80 °C
Modus 6.01:
Luftgeschwindigkeitsregelung:
Bereich: 0 bis 10 m/s
Modus 8.01:
Absolute Feuchtedifferenzregelung in g/kg
Bereich: 0 bis 50 g/kg
can be entered. Terminate again with "P". Now you are back in
Part.-No.
27/139
Start-up
P
key. Consult

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Fu-cs82937. 002/0220

Table des Matières