Programming "Protection Mode" displays an additional menu point in the Diagnostics menu.
000419:27:28
Operating time PM
11.1

Current measurements

Current measurements can be made without restrictions only on the motor side of the frequency
inverter or EC controller.
Line side measurements of the current may only be performed using true r.m.s. measuring equipment.
The line current cannot be measured with sufficient accuracy using customary measuring equipment
(for sinusoidal currents of corrected arithmetic mean).
L-BAL-E304-GB 2004
D1
Status digital input 1 (Digital In 1)
ON = terminals D1 - D1 bridged ↔ OFF = terminals D1 - D1 not bridged
D2
Status digital input 2 (Digital In 2)
ON = terminals D2 - D2 bridged ↔ OFF = terminals D2 - D2 not bridged
K1
OFF = relay K1 de-energized: terminals 11 - 12 bridged
ON = relay K1 energized: terminals 11 - 14 bridged
K2
OFF = relay K2 de-energized: terminals 21 - 22 bridged
ON = relay K2 energized: terminals 21 - 24 bridged
Operating h group1
Display of operating hours for group 1
Operating h group2
Display of operating hours for group 2
Operating h group3
Display of operating hours for group 3
Operating h group4
Display of operating hours for group 4
Operating hours for active "Protection Mode" (emergency mode)
The time (h:m:s) starts to increment as soon as Protection Mode is active.