Group Variant 2: One Controlled Group And Up To Three Switched Groups - Helios FU Comfort Sinus Manuel De Montage Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Specification FU Comfort Sinus
9.8.9.3

Group variant 2: One controlled group and up to three switched groups

Control group 2/3/4 via relais
Controller Setup
50 %
Group 2 ON value
Controller Setup
45 %
OFF Value Group2
Controller Setup
20 %
nmin at Group2
Controller Setup
70 %
Group 3 ON value
Controller Setup
65 %
OFF Value Group3
Controller Setup
30 %
nmin at Group3
Controller Setup
85 %
Group 4 ON value
Controller Setup
80 %
OFF Value Group4
Controller Setup
40 %
nmin at Group4
* As long as in IO Setup "K Function" not programmed display:
Higher settings must be selected for following groups and the switch-off value of the group must be
below the switch-on value.
L-BAL-E304-GB 2004
Group 2 ON value
Switch-on value for Group2
Setting range: 0 - 100 %
Factory setting: 50 % *
OFF Value Group2
Switch-off value for group2
Setting range: 0 - 100 %
Factory setting: 45 % *
nmin at Group2
Minimum Value for Group2
Setting range: 0 - 100 %
Factory setting: 20 % *
Group 3 ON value
Switch-on value for Group3
Setting range: 0 - 100 %
Factory setting: 70 % *
OFF Value Group3
Switch-off value for group3
Setting range: 0 - 100 %
Factory setting: 65 *
nmin at Group3
Minimum Value for Group3
Setting range: 0 - 100 %
Factory setting: 30 % *
Group 4 ON value
Switch-on value for Group4
Setting range: 0 - 100 %
Factory setting: 85 % *
OFF Value Group4
Switch-off value for group4
Setting range: 0 - 100 %
Factory setting: 80 % *
nmin at Group4
Minimum Value for Group4
Setting range: 0 - 100 %
Factory setting: 40 % *
Part.-No.
58/139
|
|
- - - -
Programming