Installation and Operating Specification FU Comfort Sinus
Menu overview for "AI3" and "AI6"
Analog In
AI1 (0.00V, 2A)
AI2 (10.00V, 1A)
AI3 (OFF)
AI4 (OFF)
AI5 (OFF)
AI3
AI3
AI3
AI3
Invertierung
Overview of possible analog inputs
Analog In
AI1 (32.7 °C)
AI2 (16.8 °C, 5E)
AI3 (OFF)
AI4 (OFF)
AI5 (OFF)
AI6 (OFF)
Setting for desired function (AI3-AI6)
Function
OFF
1E
4E
L-BAL-E304-GB 2004
P↓ ↑ ESC
OFF
P
Function
▲ ▼
▲ ▼
0-10V
P
Analog In
▲ ▼
▲ ▼
n.a.
P
Signal
▲ ▼
▲ ▼
OFF
P
▲ ▼
Example to explain the display
32.7 °C = Current temperature measured at "AI1"
16.8 °C = Current temperature measured at "AI2"
5E = Programmed function (E1 difference) for "AI2"
OFF = No function assigned
OFF = No function assigned
OFF = No function assigned
OFF = No function assigned
Description Function
No function
For mode speed controller
Operation with a second setting signal (switch over "E1" <-> "E2" via floating contact)
Operation with a second setting signal and automatic control at the higher level ("E1" <-
> "E2")
Overview of possible analog in-
puts
Setting of the desired function
Signal type setting: 0-10V, 0-
20mA, 4-20mA, TF, PT1000
Assignment: Virtual input / ac-
tual input
Inverting input
1.01