Installation and Operating Specification FU Comfort Sinus
Information
•
Addressing is performed by an external terminal or a PC with the appropriate software (automatic
addressing following chapter).
•
The MODBUS register description and the information sheet "Network structure of MODBUS" can
be requested from our Support Department V-STE for control systems - ventilation.
5.13.2
Automatic addressing
Automatic addressing can be performed by a PC with ZAset software. The connections "ID1" and
"ID2" for "addressing" are connected with each other additionally next to the bus connection for this.
This means that it is no longer necessary to address every single member manually in the network.
On the first client that is connected directly to the terminal or the PC, "GND" and "ID1" or "ID2" must be
bridged. This is recognised as a result and occupied by address 1.
For the following clients the connection "ID1" or "ID2" of a client respectively is connected with
connection "ID1" or "ID2" of the next client.
The automatic addressing of other clients is initiated by the previous client via this connection.
Example for automatic addressing via USB converter
On the USB-485 converter connection to the terminals: A (D+), B (D-) and GND.
Connection of the clients via the terminals: A (D+), B (D-), GND and ID1 / ID2
L-BAL-E304-GB 2004
Shield connection correct
USB-485-Mini/OP
GND (X)
A
(D+)
B
(D-)
MODBUS
(RS-485)
A
B
ID1
GND
ID2
(D+)
(D-)
Shield connection incorrect
USB
Part.-No.
20/139
Electrical installation
MODBUS
(RS-485)
A
B
ID1
GND
ID2
(D+)
(D-)
v_modbus_autoadr_zaset.vsd
11.11.2013