Installation and Operating Specification FU Comfort Sinus
9.9.6.1
Enable ON/OFF function
Remote control (electronic switch-off) and Reset after motor fault by potential-free contact. The power
unit is switched off electronically, the device can still be operated in the off state. Signal inputs and
outputs remain active.
When operating with two control circuits, the switch-off affects both outputs, i.e. the inverter output of
control circuit 1 and the signal output 0 - 10 V of control circuit 2.
A programmed operating indicator relay (factory set "K1 function" =
A programmed alarm relay (factory set "K2 function" =
Info
OFF
Display for switch-off alter-
nately with actual value dis-
play
Attention!
No disconnection (isolation) when turned off, in accordance with VBG4 §6)!
9.9.6.2
External message, function
Connecting an external alarm indication (via floating contact). The device continues to work un-
changed during an external indication to the digital input; the alarm symbol appears in the display.
This indication can be issued via the relay contacts (K1 K2) (see IO Setup function K1, K2).
Info
External error
Display alternating with ac-
tual value display
9.9.6.3

Limit ON / OFF, Function

The value for "Limit" adjusted in the Controller Setup, is activated over a digital input.
Contact e.g. at ditgital input "Digital In 1" (depending on device type at terminals "D1" - "D1"or "D1" -
"24 V").
For "D1" Inverting "OFF", limitation active at closed contact.
The limitation influences both outputs in operation with two control circuits.
1 Setting "Limit" (depending on device type in: %, Hz, rpm)
L-BAL-E304-GB 2004
|
|
1D
STOP
STOP
Display
for switch OFF
"OFF"
Controller
"ON"
Controller
tory setting).
At "D1 Inverting" = "ON" reversed function,
i.e. device "OFF" when contact closed.
|
|
2D
Indication during closed contact (factory setting):
Indication during opened contact:
Alternative display texts for error message see Controller Setup / display text for
external message.
|
|
3D
Controller
24V
D1 D1
0
1
Part.-No.
|
|
2 K
) does not report the switch-off.
with opened contact
for closed contact (fac-
Contact at digital input e.g. "Digital In 1"
"D1 Inverting"
1
- - - - -
1
n = 0- 80 %
0
n = 0- 100 %
77/139
Programming
|
|
1K
) reports the switch-off.
Digital In 1
Digital In 1
D1
D1
D1
D1
14.05.2019
v_1d_freigabe_d1_d1.vsd
ON
OFF
"D1 Inverting"
"OFF "
=
"ON"
=
10.05.2007
v_3d_limit.vsd