Installation and Operating Specification FU Comfort Sinus
Maximum cross sections of terminals for power section
Type
FU-CS2.5
FU-CS8
FU-CS10
FU-CS18
FU-CS22
FU-CS32
FU-CS40
FU-CS50
Possible cross sections of terminals for control section
For all types
Control
Indication relays
MODBUS
5.3

EMC-compatible installation

5.3.1

Motor cable

The applicable standard for interference emissions is EN 61000-6-3. Compliance with this standard is
achieved through the use of an unscreened motor feed cable.
5.3.2

Control cables

Pay attention to sufficient distance from powerlines and motor wires to prevent interferences. The
control cable may not be longer than 30 m. Screened control cables must be used when the cable
length is longer than 20 m. When using a shielded cable connect the shielding to one side only, i.e.
only to the control unit with the protective ground (keep cable short and with as little inductance as
possible!).
5.3.3
Harmonics current for devices ≥ 4 and ≤ 16 A
According to EN 61000-3-2 these devices are to be classified as "professional" devices.
Connection to a low voltage supply (public networks) is allowed insofar as this has been clarified with
the respective energy supply company responsible.
5.3.4
Harmonics current and line impedance for devices > 16 A and ≤ 75 A
Extract from EN 61000-3-12, valid for equipments with rated current > 16 A and ≤ 75 A, connected to
public low-voltage systems.
This equipment complies with IEC 61000-3-12 provided that the short-circuit power S
to R
x S
SCE
equ
It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution
network operator if necessary, that the equipment is connected only to a supply with a short-circuit power S
greater than or equal to R
S
Short-circuit power from line at the interface point between the user's supply and the public system
SC
S
Rated - apparent power for three phase devices: S
equ
= phase to phase voltage se Technical data "Line voltage")
(U
I
(I
= rated current of the device se Technical data "Rated current input")
equ
R
Short-circuit ratio
SCE
For this devices: R
L-BAL-E304-GB 2004
Line
rigid
2
2,5 mm
2
2,5 mm
2
2,5 mm
2
4 mm
2
6 mm
2
16 mm
2
25 mm
2
25 mm
rigid
2
0,25 - 1,5 mm
2
0,08 - 2,5 mm
2
0,14 - 1,5 mm
at the interface point between the user's supply and the public system.
x S
.
SCE
equ
≥ 120
SCE
flexible
rigid
2
2,5 mm
2,5 mm
2
2,5 mm
2,5 mm
2
2,5 mm
2,5 mm
2
4 mm
4 mm
2
6 mm
6 mm
2
10 mm
10 mm
2
16 mm
16 mm
2
16 mm
16 mm
flexible
2
0,25 - 1,5 mm
2
0,08 - 2,5 mm
2
0,14 - 1,5 mm
= √3 x U
x I
equ
I
Part.-No.
15/139
Electrical installation
Motor
flexible
2
2
2,5 mm
2
2
2,5 mm
2
2
2,5 mm
2
2
4 mm
2
2
6 mm
2
2
6 mm
2
2
10 mm
2
2
10 mm
is greater than or equal
SC
equ
SC