Installation and Operating Specification FU Comfort Sinus
5.9
Analog output (0 - 10 V) "A1"
The analogoutputs 0 - 10 V can be allocated with various functions (see IO Setup: Analog output "A").
Connection to terminal "A" - "GND" = "Analog Out" (I
It is not permissible to connect outputs of several devices to each other!
5.10
Voltage supply for external devices (+24V, GND)
A voltage supply is integrated for external devices e.g. a sensor (max. current load see technical
data).
In case of overload or short circuit (24 V – GND), the external power supply is shut down (multi-fuse).
The device performs a "Reset" and continues operation.
•
It is not permissible to connect voltage outputs of several devices to each other!
•
It is not permissible to connect voltage outputs in the device to each other!
5.11
Digital inputs (D1, D2)
Different functions can be assigned to the digital inputs "D1"and "D2" (see IO Setup: Functional
overview of digital inputs). Activation via floating contacts, a low voltage of approx. 24 V DC is
connected.
Danger due to electric current
Never apply line voltage to the digital input!
Note the input resistance (see technical data).
5.12
Relay outputs (K1, K2)
Various functions can be allocated to the relay outputs "K1" and "K2" (see IO Setup: function and
inverting relais outputs). Max. contact rating see technical data and connection diagram.
Relays K1
•
Connection of the floating contacts of relay "K1" to the terminals 11, 14, 12.
•
"K1 Function" factory setting:
fault, for enable "OFF" de-energized.
Relays K2
•
Connection of the floating contacts of relay "K2" to the terminals 21, 24, 22.
•
"K2 Function" factory setting:
for enable "OFF".
5.13
Communication
5.13.1
RS-485 interface for MODBUS
The device comes equipped with a RS-485 interface for networking via MODBUS. Conntection at: "A
(D+)", "B (D-)" and "GND".
The connections for MODBUS "A (D+)", "B (D-)" are available double and are connected with each other internally.
L-BAL-E304-GB 2004
|
|
1K
= Operating indication. I.e. energized for operation without
|
|
= Fault indication. I.e. energized for operation without fault and
2K
MODBUS
MODBUS
(RS-485)
(RS-485)
A
B
A
B
GND
ID1
GND
ID2
(D+)
(D-)
(D+)
(D-)
Part.-No.
see technical data / connection diagram).
max
MODBUS
(RS-485)
A
B
GND
ID1
(D+)
(D-)
18/139
Electrical installation
MODBUS
(RS-485)
A
B
GND
ID2
(D+)
(D-)
11.03.2014
v_am_modbus_connect.vsd