Installation and Operating Specification FU Comfort Sinus
E2 functions for activating control circuit 2:
E2 Function
Temperature
(8E)
Cold-Pressure
(9E)
Cold-Temperature
(10E)
Air Pressure
(11E)
Air flow
(12E)
Air speed
(13E)
When activating control circuit 2, the "Setting" menu group is extended.
The additional parameters for control circuit 2 are identified by a prefixed "2." e. g. "2.Setpoint 1".
A prefixed "1." e. g. "1.Setpoint 1" is added to the parameters for control circuit 1.
Example: Second control circuit for pressure control
E2 function =
Setting
20.0 °C
1.Setpoint 1
Setting
- - - - -
1.Setpoint 2
Setting
5.0 K
1. Pband 1
Setting
OFF
1. Min. Speed
Setting
50.0 Hz
1. Max. Speed
Setting
100.0 Pa
2.Setpoint 1
L-BAL-E304-GB 2004
Function second control circuit
Temperature control
Presettings and sensor selection see
Function not permitted!
Function not permitted!
Pressure control Airconditioning
Presettings and sensor selection see
Function not permitted!
Air velocity control
Presettings and sensor selection see
|
|
2.01
9E
, Mode
for temperature control via control circuit 1
1.Setpoint 1
Setpoint 1 for control circuit 1
Setting range with passive sensor type "TF", "PT1000" : -50.0...150.0 °C
Factory setting: 20.0 °C
1.Setpoint 2
Setpoint 2 for control circuit 1
Setting "Setpoint 2" e.g. reduced value for night operation.
Switchover Setpoint 1/2 by external contact (as long a sno allocation is carried out
|
|
Display:
- - - -
see IO Setup).
1. Pband 1
Pband 1 for control circuit 1
Setting range with passive sensor type "TF", "PT1000" : 0.0...200.0 K
Factory setting: 5.0 K
1. Min. Speed
Minimal Speed for control circuit 1
|
Setting range:
OFF
Factory setting:
1. Max. Speed
Maximal Speed for control circuit 1
Setting range: "Max.Frequency" (see Motor Setup) - "Min. Speed"
Factory setting: 50.0 Hz
2.Setpoint 1
Setpoint 2 for control circuit 2
Setting range: in measuring range of sensor
Factory setting: 100 Pa
Mode 2.01
Mode 4.01
Mode 6.01
|
→ "Shutdown Freq." (see Motor Setup) - "Max. Speed".
|
|
OFF
Part.-No.
24/139
Base setup
Factory setting
E2 Analog
2.Setpoint 1
In
TF / LTR,
20.0 °C
LTK, LTA
MBG0-30
15.00 bar
35.0 °C
MBG0-30
DSG200
100.0 Pa
3
DSG200
44720 m
h
MAL1
0.50 m/s