Helios FU Comfort Sinus Manuel De Montage Et D'utilisation page 189

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Specification FU Comfort Sinus
Info
0 °C
E1-E2 actual
Info
0 °C
Control value
Info
49.9 °C
Average E1/E2
Info
0 °C
E1 Actual
Info
0 °C
E2 Actual
Info
0 °C
Setpoint1
Info
100.0 Pa
Setpoint control
Info
0.0 Hz
Frequency
Info
0 %
1. Control
Info
0.0 A
Motor current
Info
0 %
Modulation
L-BAL-E304-GB 2004
Info for mode controller
Only for mode
2.05
,
8.01
Current actual value difference sensor 1 - sensor 2 (unit depending on the program-
ming).
2.04
Only in mode
(E2 function =
The highest value determined automatically from two sensor measuring values which
is used as the actual value for the control (unit depending on programming).
2.04
Only for mode
programmed for averaging (E2 function =
Current actual value measured at sensor 1 (unit depending on programming).
Display for "actual value 2" for operation with two sensors.
Display if function not active:
Display of the active target value at which the device operates.
"Setpoint1" Menu "Setting"
"Setpoint2" Menu "Setting"
"Ext. Setpoint" = setting by external signal 0-10 V. With activated manual mode the
display constantly changes between actual value and value for manual mode.
Display for operation with two control circuits:
"1.Setpoint 1" or "1.Setpoint 2" for control circuit 1
"2.Setpoint 1" or "2.Setpoint 2" for control circuit 2
4.02
Only for mode
, with setpoint depending on outdoor temperature (E2 function =
|
|
6E
).
Inverter output frequency.
"2. Modulation" for control circuit 2
(Only active in operation with a second control circuit)
Display of motor current (Metering precision approx. +/-10 %)
Display 0...100 %
0...Max. Frequency (see Motor Setup)
Part.-No.
50/139
2.01
...
8.01
|
|
4E
)
|
|
- - - - -
Programming
|
|
3E
).

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Fu-cs82937. 002/0220

Table des Matières