Installation and Operating Specification FU Comfort Sinus
Example for temperature regulation; for other modes of operation settings in corresponding sensor
unit.
Offset 1 for alarm during exceeding
ON = 15°C + 5 K = 20 °C
30
28
26
24
22
20
18
16
14
12
10
1
3
5
7
9
11
ON
Example: Setpoint 15.0 °C, Offset +5.0 K, Hysteresis 2.0 K
9.11

Motor Setup

Main menu
Controller Setup
IO Setup
Limit
Motor Setup
Diagnostic
9.11.1

Setting motor rated current

Motor Setup
32 A
MotorRatedCurr.
9.11.2

Setting motor rated voltage

Motor Setup
400 V
MotorRatedVolt.
L-BAL-E304-GB 2004
OFF = 20°C - 2 K = 18 °C
13
15
17
19
21
23
25
27
29
[min]
ON
ON
Motor Setup
MotorRatedCurr.
Possible setting for the motor rated current.
The setting for the "DC brake level" (setting brake behaviour) refers to this setting.
Setting range: 0.0...device rated current / A
Factory setting: device rated current
MotorRatedVolt.
When commissioning, you must set the motor to the rated voltage stated on the rating
plate.
An adaptation can be made if the motor rated-voltage as the applied mains voltage is
lower (e.g. 3 ~ 230 V motor on 3 ~ 400 V mains).
Verify the output voltage using suitable measuring instruments.
Setting range: 0...500 V
Factory setting: 400 V
Offset 2 for alarm during undercutting
OFF = 15°C + 2 K = 17 °C
30
28
26
24
22
20
18
16
14
12
10
1
3
5
7
Example: Setpoint 15.0° C, Offset -5.0 K, Hysteresis 2.0 K
Part.-No.
87/139
Programming
ON = 20°C - 5K = 15 °C
9
11
13
15
17
19
21
23
25
[min]
ON
27
29
ON