Setting For Operation Modes 4.01 - Helios FU Comfort Sinus Manuel De Montage Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Specification FU Comfort Sinus
Base setup
OFF
E2 Function
9.3.2
Setting for operation modes
4.01
Pressure control, Setting Setpoint in Pa
4.02
Pressure control setpoint depending on outdoor temperature
Main menu
Start
Setting
Protocol
Base setup
Controller Setup
Setting
250 Pa
Setpoint1
Setting
- - - - -
Set Internal2
Setting
250 Pa
Pband
Setting
OFF
Min. Speed
Setting
50.0 Hz
Max. Speed
L-BAL-E304-GB 2004
E2 Function
The second signal input is not activated at the factory for modes with one sensor.
In modes with two sensors, the function is automatically programmed. The second
analog input is thus assigned and no other function assignments are possible.
Modes with two sensors
4.02
For
E2 Function at
Preprogrammed sensor type
"E2 Function"
Adjustable
• |
|
1E
= External setpoint e.g. by external signal (0 - 10 V) instead of setting
"Setpoint 1"
. 0 - 10 V
• |
|
2E
= External manual operation via external signal (0 - 10 V). Switching between
setting on the device and external manual operation via digital input (
|
|
7D
Function
).
• |
|
3E
= Sensor average to E1
• |
|
4E
= Sensor comparison to E1
• |
|
5E
= Sensor difference to E1
• |
|
7E
= Measurement value = Measurement value e.g. for limit indication, display in
"E2 Actual"
Info menu
.
• |
|
|
|
8E
13E
...
= sensor input for control circuit 2
with second control circuit.
4.01
...
4.02
Setting
Setpoint1
Setting range: in measuring range of sensor
Factory setting: 250 Pa
Set Internal2
Setting "Setpoint 2" e.g. reduced value for night operation.
Switch over Setpoint 1/2 over external contact (display as long as noch allocation is
|
|
carried out:
- - - - -
IO Setup).
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
Setting range: in measuring range of sensor
Factory setting: 250 Pa
Min. Speed (basic speed only when needed)
|
|
→ "Shutdown Freq." (see Motor Setup) - "Max. Speed."
Setting range:
OFF
|
|
Factory setting:
OFF
Max. Speed (speed limitation only when needed)
Setting range: "Max.Frequency" (see Motor Setup) - "Min. Speed"
Factory setting: 50.0 Hz
Part.-No.
42/139
|
|
6E
preprogrammed = sensor for setpoint lowering.
"TF.. "
for Modes with one sensor
0 - 100 % sensor measuring range.
base setup / operation
Programming
IO Setup:

Publicité