Installation and Operating Specification FU Comfort Sinus
Display
Relais switches **
Symbol
Operation Fault
Earth fault
IGBT temp.
IGBT Fault
Sinefilter
Overload 2
DC overvoltage
AC overvoltage
AC undervoltage
DC undervoltage
Peak current
Filterchoke
External error
L-BAL-E304-GB 2004
Possible cause
Short-circuit at motor connection to
1
1
earth
Temperature of the heat sink too
1
1
high
Overload shutoff
1
1
Short-circuit between the motor
lines
Sine filter temperature too high
1
1
(only in version with integrated sine
filter)
The device was operated for too
1
1
long with too high current (> rated
current).
0
1
To high DC-link voltage
0
1
Line voltage too high
0
1
Line voltage too low
0
1
DC-link voltage too low
1
1
Current above defined limit
1
1
Input choke temperature too high
0
selectable Alarm from external contact
Part.-No.
117/139
Reaction of Controller
Adjustment
The device switches off, restarts after
approx. 60 s.
Final switch-off after three successive at-
tempts (resp. < 60 s).
Check motor and motor connection
cable.
Reset by disconnecting the line voltage.
The device switches off and switches
back on when the temperature drops.
Check cooling of the device (IGBT tem-
perature
Diagnostics menu).
The device switches off, restarts after
approx. 60 s.
Final switch-off after three successive at-
tempts (resp. < 60 s).
Check motor and motor connection
cable.
Reset by disconnecting the line voltage.
The device switches off and switches
back on when the temperature drops.
Check cooling of the device (sine filter
Diagnostics menu).
The device switches off, restart after ap-
prox. 30 s. Final switch-off after 5 suc-
cessive attempts (resp. < 10 min), then
reset necessary.
Check high output current.
Immediate switch-off, the error is dis-
played after 75 s.
When voltage okay again, restart after 15
s.
Check line voltage.
Error is displayed after 75 s.
When voltage okay again, restart after 15
s.
Check line voltage.
Error is displayed after 75 s.
When voltage okay again, restart after 15
s.
Check line voltage.
Error is displayed after 75 s.
When voltage okay again, restart after 15
s.
Check line voltage.
The device switches off, restart after ap-
prox. 30 s. Final switch-off after 10 suc-
cessive attempts (resp. < 90 s), then
reset necessary.
Check high output current.
The device switches off and switches
back on when the temperature drops.
Check cooling of the device (filter choke
temperature
Diagnostics menu).
The device continues working un-
changed.
check contacts.