Temperature Control 2.01; Basic Setting 2.01 - Helios FU Comfort Sinus Manuel De Montage Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Specification FU Comfort Sinus
9.2
Temperature control
9.2.1
Basic setting
Main menu
Setting
Protocol
Base setup
Controller Setup
IO Setup
Base setup
2.01
Mode
Base setup
TF
E1 Analog In
Base setup
20.0 °C
E1 Offset
L-BAL-E304-GB 2004
2.01
...
2.05
2.01
...
2.05
Base setup
Mode
Mode selection e.g.
E1 Analog In
The sensor input is factory set in modes of group
(sensor type KTY81-210).
Measuring range: -50.0...+150 °C
Connection terminals: "E1" and "T"
Other settable sensors:
PT1000
at terminals
MTG-120V (type designation for active sensor with 0 - 10 V output, connection to
"E1"
terminals
,
0 - 10 V, 0 - 20 mA, 4 - 20 mA (for sensors with free measuring range and linear
characteristic)
The sensor measuring range must be entered for sensors with free measuring range in
order to display the actual value correctly.
Example with a 0 - 10 V sensor and 0 - 100 °C measurement range:
E1 Analog In = 0 - 10 V, E1 Unit = °C, E1 Decimals = 1, E1 Min. = 0,0 °C, E1 Max. =
100,0 °C,
When selecting sensors with active signal, the setpoint and the Pband are automati-
cally set to the 1/2 measuring range.
E1 Offset
Sensor calibration with calibrated comparison device.
The current "E1 Actual" is displayed including the offset set here.
2.01
"E1"
"T"
, (measuring range -50.0...+150 °C)
and
"GND"
"24 V"
, measuring range: -10...+120 °C)
and
Part.-No.
35/139
Programming
2
to sensors of the "TF" type series