Installation and Operating Specification FU Comfort Sinus

12 Protocol

12.1

Display and query of events and malfunctions

Main menu
Start
Setting
Protocol
Base setup
Controller Setup
Event types
The device distinguishes between several event types which are identified by different symbols.
Message by alarm relay depending on the type of failure and programming.
Example:
Protocol
Sensor 1
Protocol
Communication
Protocol
Motor fault
Protocol
IGBT temp.
Details of events
Example: Motor fault
Protocol
Motor fault
L-BAL-E304-GB 2004
Events during operation can lead to a malfunctioning of the device.
The last 100 events are saved in the "Protocol" menu group.
Position 1 = latest event, display: Protocol 1/100
Position 100 = last saved event, display: Protocol 100/100
The saved events are retained even after resetting to factory setting (
group Start / PIN input)!
1/10
Attention symbol = message
The message is only listed in the protocol. There is no message alternately with
the actual value display and no message via alarm relay.
Exception
In case of sensor failure there is always a message in the display (
Setup / Alarm Sensors) .
Detail
2/10
Bell symbol = error with alarm message
Errors at which the device automatically goes into operation (e.g. overload) or
stays in operation (e.g. communication errro) after clearing the fault.
The fault message is listed in the protocol and appears alternately with the actual
value display.
Detail
Cross in circle symbol = switch-off error
3/10
Errors which lead to switching off the controller output (e.g. motor overtemper-
ature). Restarting is only possible after a reset (interlock)
The fault message is listed in the protocol and appears alternately with the actual
value display.
Detail
4/10
Cross symbol = previous messages
Cause of the message no longer exists.
Detail
5/10
Press the key to show further details.
Detail
Part.-No.