Installation and Operating Specification FU Comfort Sinus
Setting
5.0 K
Pband
Setting
OFF
Min. Speed
Setting
50.0 Hz
Max. Speed
Setting
OFF
Manual mode
Setting
50.0 Hz
Speed manual
L-BAL-E304-GB 2004
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
Passive sensor type "TF", "PT1000"
Setting range: 0 - 200.0 K (Kelvin)
Factory setting: 5.0 K
active Sensor type "MTG-120V"
Setting range: -10.0...+120.0 K
Factory setting: 65.0 K
Min. Speed (basic speed only when needed)
|
|
Setting range:
OFF
→ "Shutdown Freq." (see Motor Setup) - "Max. Speed."
|
|
Factory setting:
OFF
Max. Speed (speed limitation only when needed)
Setting range: "Max.Frequency" (see Motor Setup) - "Min. Speed"
Factory setting: 50.0 Hz
Manual mode
"OFF" = automatic control as function of the set parameters (Factory setting)
"ON" = automatic control without function, speed setting in menu "Speed manual"
Speed manual
Manual speed setting without influence by the external signal.
Activation by menu "Manual mode" or external contact at digital input (see IO Setup).
Setting range: 0... "Max. Frequency" (see Motor Setup)
Factory setting: 50.0 Hz
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.