Installation and Operating Specification FU Comfort Sinus
Info
OFF
Min. switch-off
9.8
Controller Setup
Main menu
Start
Settings
Protocol
Base setup
Controller Setup
9.8.1
PIN protection activate, PIN0010
Controller Setup
OFF
PIN Protection
Available menu groups with activated PIN-protection
Main menu
Start
Setting
Protocol
If PIN-protection is switched on, it automatically becomes active after about 15 minutes without keys
being pressed.
Possibilities for early activation of PIN protection:
•
Execute the "Reset" function in the "Start" menu group.
•
By switching the mains voltage off and then on again.
Information
After installation of the device has been carried out, "PIN-Protection" should be activated = "ON"
L-BAL-E304-GB 2004
Minimum switch-off state
"ON" = switch off, if Setpoint (+/- "Min. cut off" value) is reached.
"OFF" = no switch-off, i.e. operation at minimum speed.
Display for operation with two control circuits:
"1.Minimum switch-off" for control circuit 1
"2.Minimum switch-off" for control circuit 2
Controller Setup
The adjustments for the installation in the service level can be protected against
unintentional modifications. To do this, activate the "PIN protection" = "ON".
In order to simplify the initial start-up operation, the service level in the factory setting is
free = "OFF" i.e. accessible without PIN 0010.
Part.-No.
51/139
Programming