Helios FU Comfort Sinus Manuel De Montage Et D'utilisation page 250

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Specification FU Comfort Sinus
Function
Comparison E1
(4E)
Difference E1
(5E)
Setpoint derating
(6E)
Measurement
(7E)
Temperature
(8E)
Cold-Pressure
(9E)
Cold-Temperature
(10E)
Air Pressure
(11E)
Air flow
(12E)
Air speed
(13E)
Digital outputs K1 and K2
Function
OFF
Operating indication
(1K)
Fault indication
(2K)
External error
(3K)
Limit modulation
(4K)
Limit E1
(5K)
Limit E2
(6K)
Setpoint Offset
(7K)
Group2
(8K)
Group3
(12K)
Group4
(13K)
L-BAL-E304-GB 2004
Description Function E2
Sensor comparison to E1
Sensor difference to E1
Sensor for controlled outdoor temperature
Measurement value e.g. Measurement value e.g. for limit indication, display in Info
menu "E2 Actual".
For activation of a second control circuit
(only possible in certain Modes (see operation with second control circuit)
Temperature control, pre-settings and sensor selection correspond to mode
Pressure control condensers
Pressure control for condensers with input for refrigerant
Pressure control air conditioning, pre-settings and sensor selection correspond to
4.01
mode
Air volume control
Air velocity control, pre-settings correspond to mode
Designation
No function
Relays remain always de-energized
Operating indication (factory setting for "K1", non inverting).
Operation without fault, reports enable "OFF"
Fault indication (factory setting for "K2", non inverting).
Pulled up in operation without fault, with release "OFF" not dropped out.
Drops out in case of line and device fault and external fault at the digital input. Depend-
ing on programming in event of sensor failure.
External fault separate with message at digital input (factory setting if terminals
bridged)
Limit modulation
Exceeding or undercutting the limits for modulation
Limit "E1"
When over or falling below limits for input signal "E1"
Limit "E2"
When over or falling below limits for input signal "E2"
For modes as controller higher
Setpoint Offset
Deviation between actual value and setpoint to high
Group control (Group 2)
Switching on fans depending on modulation
Group control (Group 3)
Switching on fans depending on modulation
Group control (Group 4)
Switching on fans depending on modulation
For modes as temperature controller with additional functions
Part.-No.
111/139
6.01
2.01
2.03
Menu tables
2.01

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Fu-cs82937. 002/0220

Table des Matières