Installation and Operating Specification FU Comfort Sinus
7.3
Procedure as for start-up (outside wizard)
Sequence
Check if Thermostats or Thermistors of the motor are connected to input "TB/TP In".
1
If the motor protection function of the device is not neccesary the both terminals "TB / TP" have to be bridged.
Check connection and close housing carefully.
2
Turn on mains voltage.
3
Information
In the menu group Start the adjustment for Motor is OFF for factory setting => display:
This prevents the system from inadvertently starting up before configuration is complete.
4
Switch over via
Menu group: Start
5
Set the menu language if necessary (factory setting English = Language GB).
"
The display can be switched between SI units (US units = OFF) and imperial (US) units (US units = ON).
"
Set the operating mode in the Base setup menu group (factory settings
Attention!
6
When saving the operating mode, the respective preset factory operating-mode setting is loaded. That means,
the settings you have made, e.g., in "Motor Setup" are lost. An exception: the menu language setting remains
preserved.
The Motor Setup factory installed values are for variable voltage external rotor motors 400 V / 50 Hz. After
checking of the motor data the setting are to be adapted if necessary.
Motor rated voltage
7
(see name plate)
3 ~ 400 V, 50 Hz
Additional settings see Motor Setup.
In menu group Start switch setting for Motor to " ON ".
8
Additional setings (see Programming and selected Mode).
Switch Motor to ON in menu group "Start"
1
L-BAL-E304-GB 2004
Display after first turning on the mains voltage.
|
|
Esc
to Main menue
Setting
Edgefrequency
48.5 Hz
2
3
P
Setting
4
5
▲
Part.-No.
28/139
|
|
STOP
.
1.01
= speed controllers).
Setting
Max. Frequency
50 Hz
6
7
P
Start-up