Installation and Operating Specification FU Comfort Sinus
9 Programming
Display in SI units or Imperial units (US)
The following description is for display in SI units (factory setting). The appropriate conversion factors
must be observed when switching over to Imperial units (US) (
9.1
Speed controller
9.1.1
Base setup
Main menu
Setting
Protocol
Base setup
Controller Setup
IO Setup
Base setup
1.01
Mode
Base setup
0 - 10V
E1 Analog In
Base setup
OFF
E2 Function
Base setup
- - - - -
E2 Analog In
9.1.2
Setting for operation
Main menu
Setting
Protocol
Base setup
Controller Setup
IO Setup
Setting
25.0 Hz
Set Internal1
L-BAL-E304-GB 2004
1.01
1.01
Base setup
Mode
Factory setting Mode:
E1 Analog In
Selection: 0 - 10 V, 0 - 20 mA, 4 - 20 mA (Inverting see IO Setup)
Factory setting: 0 - 10 V
E2 Function (only for special applications)
Analog input 2 "E2" factory set at "OFF".
For operation with a second setting signal and switch over by potential-free contact: E2
Function = Ext. Setpoint (1E)
Necessary function for digital input: E1/E2 (4D) see IO Setup
For operation with a second signal and automatic control at the higher level: E2
Function = comparison E1 (4E).
E2 Analog In
Display as long as no function allocated:
Selection: 0 - 10 V, 0 - 20 mA, 4 - 20 mA (Inverting, E2 BUS Modus see IO Setup)
Factory setting: 0 - 10 V
1.01
Setting
Set Internal1
Setting range manual speed setting: "Min. Speed" - "Max. Speed"
Factory setting: 25.0 Hz
1.01
|
- - - - -
Part.-No.
33/139
Programming
menu group Start / US Units).
|