For Mode 2.03 Relay Output For Temperature Monitoring - Helios FU Comfort Sinus Manuel De Montage Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Specification FU Comfort Sinus
Example:
Setpoint 15.0 °C, Offset +5.0 K, Hysteresis 2.0 K
ON = 15°C + 5 K = 20 °C
30
28
26
24
22
20
18
16
14
12
10
1
3
5
Info
28.7 °C
E1 Actual
Temperature variation with reprogramming to
the Cooling
Example:
Setpoint 15.0 °C, Offset +5.0 K, Hysteresis 2.0 K
ON = 15°C + 5 K = 20 °C
30
28
26
24
22
20
18
16
14
12
10
1
9.2.6
For mode
2.03
If the set value for the "minimum alarm" is not reached or the set value for the "maximum alarm" is
exceeded, a message is generated via the alarm symbol in the display. In addition, „Lmt E1 min" is
displayed alternately with the actual value for the minimum alarm and Lmt E1 max for the „Maximum
alarm". An external message follows via the factory-assigned"K1" relay. (IO Setup: K1 function =
|
|
2K
).
Setting
10.0 °C
Alarm Minimum
Setting
35.0 °C
Alarm Maximum
Info
GW E1 min.
L-BAL-E304-GB 2004
OFF = 20°C + 2 K = 22 °C
7
9
11
13
15
17
19
21
23
25
[min]
ON
ON
ON
The activated heating is indicated over the fire symbol in the display.
OFF = 20°C - 2 K = 18 °C
3
5
7
9
11
13
15
17
19
21
23
[min]
ON
ON
ON
Relay output for temperature monitoring
Alarm Minimum
Setting range: OFF / -49.9...150.0 °C
Factory setting: 10.0 °C
Alarm Maximum
Setting range: OFF / -49.9...150.0 °C
Factory setting: 35.0 °C
Example for display if falling below setting "Alarm Minimum" alternating to the actual
value display.
Relay "K1" disengages (if not inverted).
Example:
Setpoint 20.0 °C, Offset -5.0 K, Hysteresis 2.0 K
OFF = 15°C + 2 K = 17 °C
30
28
26
24
22
20
18
16
14
12
10
27
29
1
|
|
10K
for "K2" in IO Setup, e.g., for activation of
If the ambient temperature is higher than the set operat-
ing point, the cooling remains switched on. If the ambient
temperature falls below the set operating point of the
cooling by 2 K (Kelvin), it is switched off. I.e., the OFF
point is situated at the hysteresis value under the ON
point.
25
27
29
Part.-No.
40/139
ON = 20°C - 5K = 15 °C
3
5
7
9
11
13
15
17
19
21
23
[min]
ON
Programming
25
27
29
ON