Installation and Operating Specification FU Comfort Sinus
Setting
- - - - -
2.Setpoint 2
Setting
100.0 Pa
2. Pband 1
Setting
0 %
2. Min. Speed
Setting
100 %
2. Max. Speed
Setting
OFF
1. Manual mode
Setting
100 %
1. Speed man.
Function extension for digital inputs "D1" and "D2" in operation with second control circuit
D1 / D2 Function
E1 / E2
(4D)
2. Setpoint 1/2
(9D)
2.Setp+Pband1/2
(16D)
* Detailed description see IO Setup / Digital Inputs "D1" / "D2"
Following restrictions apply for the control circuit 2:
The "Manual Mode" function in the "Setting" menu group only influences control circuit 1!
The fuction Limit (see IO Setup
neously.
The "Max. Speed" setting by a digital input (see IO Setup
control circuits. I.e. at "1.Max. Speed" and at "2.Max. Speed".
The controller configurations (KP, KI, KD, TI see Controller Setup) are identical for both control
circuits. Fine adjustment is possible for each control circuit by the separate "Pband" setting.
L-BAL-E304-GB 2004
2.Setpoint 2
Setpoint 2 for control circuit 2
Setting "Setpoint 2" e.g. reduced value for night operation.
Switchover Setpoint 1/2 by external contact (as long a sno allocation is carried out
|
|
Display:
- - - -
see IO Setup).
2. Pband 1
Pband 1 for control circuit 2
Setting range: in measuring range of sensor
Factory setting: 100 Pa
2. Min. Speed
Minimal Speed for control circuit 2
Setting range: 0... "2. Max. Speed"
Factory setting: 0 %
2. Max. Speed
Maximal Speed for control circuit 2
Setting range: 100 %... "2. Min. Speed"
Factory setting: 100 %
Manual mode
Manual mode for control circuit 1
"OFF" = automatic control as function of the set parameters (Factory setting)
"ON" = automatic control without function, speed setting in menu "Speed manual"
Speed manual
Speed Manual mode for control circuit 1
Setting range: 0... "1. Max. Speed"
Factory setting: 100 %
Description *
The output for control circuit 2 is set additionally to "A2" to "A1" (regardless of the
|
programmed function for
A1
switching.
for control circuit 2: Switch over "Setpoint 1" / "Setpoint 2"
for control circuit 2: Switch over Setpoint 1/2 and Pband 1/2
When programming this function, "Setting" additionally lists the parameter: "2.Pband 2 for
control circuit 2"
|
|
3D
and Controller Setup) influences both control circuits simulta-
Part.-No.
25/139
|
). Control circuit 1 has no output for the duration of the
|
|
11D
) simultaneously influences both
Base setup