Installation and Operating Specification FU Comfort Sinus
Setting
- - - - -
2.Setpoint 2
Setting
100.0 Pa
2. Pband 1
Setting
0 %
2. Min. Speed
Setting
100 %
2. Max. Speed
Setting
OFF
1. Manual mode
Setting
100 %
1. Speed man.
Function extension for digital inputs "D1" and "D2" in operation with second control circuit
D1 / D2 Function
E1 / E2
(4D)
2. Setpoint 1/2
(9D)
2.Setp+Pband1/2
(16D)
* Detailed description see IO Setup / Digital Inputs "D1" / "D2"
Following restrictions apply for the control circuit 2:
•
The "Manual Mode" function in the "Setting" menu group only influences control circuit 1!
•
The fuction Limit (see IO Setup
neously.
•
The "Max. Speed" setting by a digital input (see IO Setup
control circuits. I.e. at "1.Max. Speed" and at "2.Max. Speed".
•
The controller configurations (KP, KI, KD, TI see Controller Setup) are identical for both control
circuits. Fine adjustment is possible for each control circuit by the separate "Pband" setting.
L-BAL-E304-GB 2004
2.Setpoint 2
Setpoint 2 for control circuit 2
Setting "Setpoint 2" e.g. reduced value for night operation.
Switchover Setpoint 1/2 by external contact (as long a sno allocation is carried out
|
|
Display:
- - - -
see IO Setup).
2. Pband 1
Pband 1 for control circuit 2
Setting range: in measuring range of sensor
Factory setting: 100 Pa
2. Min. Speed
Minimal Speed for control circuit 2
Setting range: 0... "2. Max. Speed"
Factory setting: 0 %
2. Max. Speed
Maximal Speed for control circuit 2
Setting range: 100 %... "2. Min. Speed"
Factory setting: 100 %
Manual mode
Manual mode for control circuit 1
"OFF" = automatic control as function of the set parameters (Factory setting)
"ON" = automatic control without function, speed setting in menu "Speed manual"
Speed manual
Speed Manual mode for control circuit 1
Setting range: 0... "1. Max. Speed"
Factory setting: 100 %
Description *
The output for control circuit 2 is set additionally to "A2" to "A1" (regardless of the
|
programmed function for
A1
switching.
for control circuit 2: Switch over "Setpoint 1" / "Setpoint 2"
for control circuit 2: Switch over Setpoint 1/2 and Pband 1/2
When programming this function, "Setting" additionally lists the parameter: "2.Pband 2 for
control circuit 2"
|
|
3D
and Controller Setup) influences both control circuits simulta-
Part.-No.
25/139
|
). Control circuit 1 has no output for the duration of the
|
|
11D
) simultaneously influences both
Base setup