Installation and Operating Specification FU Comfort Sinus
9.8.9
Group control
9.8.9.1
Group version
Groups can be controlled by the analogue output "A" or the relay outputs "K1" and "K2".
If required the add-on module type Z module B can be retrofitted. Further inputs and outputs (IOs) are
located on it, which can be used for group control.
Controller Setup
0
Group version
Information
•
The groups must be connected at the appropriate programmed output when activating by the
analogue outputs and relays.
•
The assignment of the analogue outputs and the relays for the group control takes place in the IO
Setup.
•
The number of possible groups depends on the available hardware outputs.
9.8.9.2
Group version 1: Two controlled groups
Control group 2 via 0 - 10 V output
Controller Setup
50 %
Group 2 ON value
Controller Setup
45 %
OFF Value Group2
Controller Setup
20 %
nmin at Group2
* As long as in IO Setup "A Function" not programmed to
Function
•
Group 1 continuously controlled by the device's "Master" power unit (
•
Group 2 continuously controlled by a second "Slave" power unit, this is controlled by the "Master"
by a 0 - 10 V signal. IO Setup: A Function =
L-BAL-E304-GB 2004
Following group versions are available:
0: no Group control (Factory setting)
1: Two controlled groups
2: One controlled group and up to three switched groups
Group 2 ON value
Switch-on value for Group2
Setting range: 0 - 100 %
Factory setting: 50 % *
OFF Value Group2
Switch-off value for group2
Setting range: 0 - 100 %
Factory setting: 45 % *
nmin at Group2
Minimum Value for Group2
Setting range: 0 - 100 %
Factory setting: 20 % *
|
|
Part.-No.
56/139
|
|
|
5A
, display:
- - - -
|
5A
(group control).
Programming
motor connection).