Installation and Operating Specification FU Comfort Sinus
9.5
Absolute humidity difference control
Information
For further information, see appendix Basic principles / Setting options for "Absolute humidity
difference control".
9.5.1
Base setup
Main menu
Start
Setting
Protocol
Base setup
Controller Setup
Base setup
8.01
Mode
Base setup
AFS 0-10V
E1 Analog In
Base setup
0.0 g/kg
E1 Offset
Base setup
5E
E2 Function
L-BAL-E304-GB 2004
8.01
Base setup
Mode
Mode selection
E1 Analog In
The sensor input is factory set for Mode
Measuring range: 0...50.0 g/kg
Output signal: 0 - 10 V
Connection terminals: "E1", "GND", "24V"
Input for sensors with free measuring range and linear characteristic curve adjustable
for the following standard signals:
0 - 10 V, 0 - 20 mA, 4 - 20 mA
For sensors with free measuring range, the sensor measuring range must be entered
under the following menu points in order to ensure a correct actual value display: E1
unit, E1 decimal, E1 Min., E1 Max.
E1 Offset
Sensor calibration with calibrated comparison device.
The current "E1 Actual" is displayed including the offset set here.
E2 Function
•
8.01
In mode
value between sensor 1 and sensor 2. Pre-programmed sensor: Type
10V"
.
"E2 Function"
Adjustable
•
OFF = Operation with one sensor
• |
|
1E
= External setpoint e.g. by external signal (0 - 10 V) instead of setting
"Setpoint 1"
• |
|
2E
= External manual operation via external signal (0 - 10 V). Switching between
setting on the device and external manual operation via digital input (
|
7D
Function
• |
|
3E
= Sensor average to E1
• |
|
4E
= Sensor comparison to E1
• |
|
6E
= sensor for outdoor temperature-dependent setpoint adaptation, pre-pro-
grammed sensor type
– Menu group
– Menu group
– Example see setting for operation
• |
|
7E
= Measurement value = Measurement value e.g. for limit indication, display in
"E2 Actual"
Info menu
• |
|
|
8E
13E
...
with second control circuit.
8.01
8.01
8.01
the E2 function is preprogrammed to
(alternative)
. 0 - 10 V
0 - 100 % sensor measuring range.
|
).
"TF.."
.
"Setting"
additional parameter: T-Band, T-Start SA, Min. Setpoint.
"Info"
additional parameter: Setpoint control
4.01
.
|
= sensor input for control circuit 2 see Base setup / operation
Part.-No.
46/139
Programming
to sensor type "AFS 0-10V".
|
|
5E
= Control on difference
"AFS 0-
4.02
...
additional menu items.
IO Setup: