Setting; Settings For Absolute Humidity Difference Control - Helios FU Comfort Sinus Manuel De Montage Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Specification FU Comfort Sinus
Fast modulation:
Sensor output 0 - 50 g/kg.
A control range of 5 corresponds to an output of 100 % output frequency.
Thus 0 - 5 g/kg corresponds to control from 0 - 100 % output frequency.
From 5 g/kg the maximum modulation is achieved at 100 % output frequency.
To achieve an output value of 100 % output frequency, the difference must be 5 g/kg.
Alternative to power output 0 - 100 % output frequency, control with on/off signal via relay
As an alternative to the power output with 0 - 100 % output frequency, an on/off signal can be used to
control a fan via a relay in the FU-C.
To boost the power of the FU-C relay, a contactor corresponding to the fan current must be selected.
If there is a difference, which means venting for drying is worthwhile, the relay is switched on. The fan
is switched on accordingly.
Forced ventilation independent of control
Independently of the difference control, a digital input on the FU-C, e.g. a light switch to be set by the
customer, can be used to activate forced ventilation mode.
13.4.5

Setting

13.4.5.1

Settings for absolute humidity difference control

Control of fans using the power output with 0 - 100 % output frequency.
The settings specified below are already saved on delivery (factory setting)
Base setup menu
Mode
E1 Analog In
E1 Unit
E1 Decimals
E1 Min.
E1 max
E1 Offset
E2 Function
E2 Analog In
E2 Unit
E2 Decimals
E2 Min.
E2 Max.
E2 Offset
Setting menu
Setpoint1
L-BAL-E304-GB 2004
Value
Meaning
8.01
Control on difference between sensor 1 and sensor 2,
E1-E2
AFS 0-10V
Helios type humidity sensor at E1
(the following E1 parameters (unit, decimal, min. and
max.) are fixed settings when using the Helios sensor,
i.e. settings are not possible)
- - - - -
g/kg
- - - - -
One decimal place displayed
- - - - -
Scaling 0 g/kg
- - - - -
Scaling 50 g/kg
0.0
Signal shift
5E
Difference E1-E2
AFS 0-10V
Helios type humidity sensor at E2
(the following E1 parameters (unit, decimal, min. and
max.) are fixed settings when using the Helios sensor,
i.e. settings are not possible)
- - - - -
g/kg
- - - - -
One decimal place displayed
- - - - -
Scaling 0 g/kg
- - - - -
Scaling 50 g/kg
0.0
Signal shift
Value
Meaning
0 g/kg
Setpoint 1 = Initial value
(suggestion)
No control takes place at a variation of 0. If the variation
is >0 control starts.
100% = 10 V output depends on the set control range.
To compensate for tolerances in the measurement
chain, the initial value can be set to e.g. 0.5 instead of
0. Control thus begins from 0.5 g/kg.
Part.-No.
125/139
Enclosure

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Fu-cs82937. 002/0220

Table des Matières