Settings For Operation Modes 6.01 - Helios FU Comfort Sinus Manuel De Montage Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Specification FU Comfort Sinus
9.4.2
Settings for operation modes
6.01
Air velocity control, Setpoint in m/s
Main menu
Start
Setting
Protocol
Base setup
Controller Setup
Base setup
5.0 m/s
Setpoint1
Base setup
- - - - -
Set Internal2
Base setup
5.0 m/s
Pband
Setting
OFF
Min. Speed
Setting
50.0 Hz
Max. Speed
Setting
OFF
Manual mode
Setting
50.0 Hz
Speed manual
L-BAL-E304-GB 2004
6.01
Setting
Setpoint1
Setting range: in measuring range of sensor
Factory setting: 5.0 m/s
Set Internal2
Setting "Setpoint 2" e.g. reduced value for night operation.
Switch over Setpoint 1/2 over external contact (display as long as noch allocation is
|
|
carried out:
- - - - -
IO Setup).
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
Setting range: in measuring range of sensor
Factory setting: 5.0 m/s
Min. Speed (basic speed only when needed)
|
|
→ "Shutdown Freq." (see Motor Setup) - "Max. Speed."
Setting range:
OFF
|
|
Factory setting:
OFF
Max. Speed (speed limitation only when needed)
Setting range: "Max.Frequency" (see Motor Setup) - "Min. Speed"
Factory setting: 50.0 Hz
Manual mode
"OFF" = automatic control as function of the set parameters (Factory setting)
"ON" = automatic control without function, speed setting in menu "Speed manual"
Speed manual
Manual speed setting without influence by the external signal.
Activation by menu "Manual mode" or external contact at digital input (see IO Setup).
Setting range: 0... "Max. Frequency" (see Motor Setup)
Factory setting: 50.0 Hz
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
Part.-No.
45/139
Programming