Installation and Operating Specification FU Comfort Sinus
Procedure in start-up wizard
Sequence
1
2
3
4
5 *
(6) *
7 *
8 *
* Additional parameters with Protection Mode programmed (extended start-up wizard)
Display after completed programming
0.0 Hz
Frequency
Notes on further programming:
Modifying the speed setting, see setting for mode
Adaptation of inputs and outputs, see "IO Setup". The digital input "D1" is preset for enabling the
device. To allow the device to start in standby mode, the contact at terminals "D1-D1" must be
closed.
In the "Start" menu group, the factory setting for the motor is "OFF". To allow the device to start in
standby mode, you can switch to "ON".
Information
If emergency mode is activated (contact at terminals "D2-D2" closed) the device starts even if it is not
enabled via input "D1" and if the motor setting = OFF in the "Start" menu group.
L-BAL-E304-GB 2004
Menu point
D
Language
32 A
MotorRatedCurr.
OFF
Protection Mode
0000
PIN input
External
PM specification
50.0 Hz
PM specification
2 sec
Rampup time PM
8 sec
Rampdown time PM
The display switches between actual
value and OFF
Setting
Menu language
MotorRatedCurr.
OFF => ON
|
|
PIN input
6006
Type of speed setting with Protection Mode (emergency mode) acti-
vated
External: Variable speed setting via external signal
Internal: Constant speed (see subsequent parameter)
Constant speed with "PM specification" = "Internal setting"
Setting range: 20.0...50.0 Hz
Factory setting: 50.0 Hz
Set ramp-up time with "Protection Mode" (emergency mode) acti-
vated
Setting range: 0...350 sec.
Factory setting: 2 sec.
Set rampdown time with "Protection Mode" (emergency mode) acti-
vated
Setting range: 0...350 sec.
Factory setting: 8 sec.
1.01
.
Part.-No.
130/139
Enclosure