Installation and Operating Specification FU Comfort Sinus
9.8.5

Limit

Controller Setup
- - - - -
Limit
"Limit value" = max. possible modulation (e.g.
speed reduction during night operation by
time switch).
Setting range: "Limit" = "n-max" up to "n-min".
Factory setting: 100 %
e. no limit.
Setting depending on device tye in: % or rpm.
9.8.6

Minimum switch-off

Controller Setup
OFF
Min. switch-off
Minimum switch-off = OFF (factory setting)
If no "Min. speed" is adjusted, the fan stops with
reaching the desired value.
If "Min. speed" is adjusted (e.g. 20%), then no dis-
connection of the fan takes place. I.e., always a
minimum ventilation is ensured (fan does not go
under setting "Min. speed").
Minimum switch-off, e.g. -2.0 K
It takes place a disconnection from setting "Min.
speed"to "0", if the given difference is reached re-
lated to the desired value.
At a plus value (+) before reaching the desired value
At a minus value (-) after falling below the desired
value.
L-BAL-E304-GB 2004
After allocation of a digital input (
can be activated via a digital input ("D1", "D2", ..).
Display as long as no allocation has been carried out in "IO Setup":
The limitation influences both outputs in operation with two control circuits.
max. modulation, i.
Limit (idealized principle diagram)
nM Motor speed
L Limit
S Setpoint
R Pband
D Speed controller: setting signal
P P-controller: control deviation
This function is primarily significant for installation of the device as a pure P Controller
in refrigeration and air-conditioning technology.
For operation mode speed controller
Display for operation with two control circuits:
"1.Minimum switch-off" for control circuit 1
"2. Minimum switch-off" for control circuit 2
Part.-No.
53/139
IO Setup) an adjustable limitation of the modulation
nM
100 %
L
50 %
Min.
0 %
50 %
I
S
R
1.01
without function!
nM
100 %
50 %
-2.0 K
Min.
20 °C
S
Minimum cut off (idealized principle diagram)
nM Motor speed
S Setpoint
R Pband
I Actual value
Programming
|
|
- - - -
L= 70% Min.= 0 % Max. = 100 %
L = 70% Min. = 35 % Max. = 85 %
25.03.2013
v_limit.vsd
100 %
D
I
P
Min. 35 %
Max. = 100 %
I
10.05.2007
7 K
27 °C
v_min_luft_abschalt.vsd