Installation and Operating Specification FU Comfort Sinus
Info
Lmt E1 max.
9.3
Pressure control airconditioning
9.3.1
Base setup
Main menu
Start
Setting
Protocol
Base setup
Controller Setup
Base setup
4.01
Mode
Base setup
DSG500
E1 Analog In
Base setup
0.0 Pa
E1 Offset
L-BAL-E304-GB 2004
Example for display if exceeding setting "Alarm Maximum" alternating to the actual
value display
Relay "K1" disengages (if not inverted).
4.01
...
4.02
Base setup
Mode
Mode selection e.g.
E1 Analog In
The sensor input is factory set for modes of group
Measuring range: 0...500 Pa
Output signal: 0 - 10 V
Connection terminals: "E1", "GND", "24V"
Other settable sensors / measuring ranges:
"DSG 50"
"DSG100"
,
"DSG1000"
,
measuring range [Pa], output signal 0 - 10 V).
0 - 10 V, 0 - 20 mA, 4 - 20 mA (for sensors with free measuring range and linear
characteristic)
The sensor measuring range must be entered for sensors with free measuring range in
order to display the actual value correctly.
Example with a 0 - 10 V sensor and 0 - 400 Pa measurement range:
E1 Analog In = 0 - 10 V, E1 Unit = Pa, E1 Decimals = 1, E1 Min. = 0,0 Pa, E1 Max. =
400 Pa
E1 Offset
Sensor calibration with calibrated comparison device.
The current "E1 Actual" is displayed including the offset set here.
4.01
...
4.02
4.01
"DSG200"
"DSG300"
,
,
"DSG2000"
"DSG4000"
,
,
Part.-No.
41/139
4
to sensor type "DSG500 ".
"DSG500 / LDF500"
,
"DSG6000"
(numerical specification
Programming
,