AVENTICS | Bus Coupler AES/Valve Driver AV, Ethernet POWERLINK | R412018143–BAL–001–AF
12.5.4
 Have you mounted at least 4 valve positions after the first pneumatic supply plate?
 Have you mounted a maximum of 64 valve positions?
 Have you integrated no more than 32 electrical components? Note that an AV-EP pressure
 Have you mounted at least two valves after every pneumatic or electrical supply plate that marks
 Have you always installed the valve driver boards to be in line with the base plate limits, i.e.
 Have you integrated no more than 8 AV-EPs?
If you have answered "Yes" to all these questions, you may proceed with the documentation and
configuration of the valve system.
12.5.5
PLC configuration key
After a conversion, the PLC configuration key printed on the right end plate is no longer valid.
Mat. no.
After a conversion, the material number (MNR) on the right end plate is no longer valid.

12.6 Conversion of the I/O zone

12.6.1
No more than ten I/O modules may be connected to the bus coupler.
For further information on converting the I/O zone, see the system descriptions of the individual
I/O modules.
12.6.2
The PLC configuration key is printed on the top of the I/O modules.

Reviewing the valve zone conversion

Following the conversion of the valve zone, use the following checklist to determine whether you
have complied with all rules.
regulator corresponds to three electrical components.
the start of a new section?
– One base plate, 2x, is installed with one valve driver board, 2x,
– Two base plates, 2x, are installed with one valve driver board, 4x,
– One base plate, 3x, is installed with one valve driver board, 3x,

Conversion documentation

Correct the PLC configuration key or cover it with a new label and write the new PLC
configuration key on the end plate.
Always document all changes to your configuration.
Mark the material number so that it is clearly visible that the unit no longer corresponds to its
original condition on delivery.

Permissible configurations

We recommend an expansion of the I/O modules starting from the left end of the valve system.
Conversion documentation
Always document all changes to your configuration.
121
Conversion of the Valve System