AVENTICS | Bus Coupler AES/Valve Driver AV, Ethernet POWERLINK | R412018143–BAL–001–AF
Presettings on the Bus Coupler
Address on delivery
S1
S2
9.2

Assigning a POWERLINK address

The bus coupler requires a unique IP address in the Ethernet POWERLINK network in order
to be detected by the controller.
Danger of injury if changes are made to the settings during operation.
Uncontrolled movement of the actuators is possible!
Never change the settings during operation.
On delivery, the switches are set to address assignment via the "Browse and Config" tool (0x00).
Switch S2 is set to 0 and switch S1 to 0.
9.2.1

Manual address assignment with address switch

Fig. 5:
Address switches S1 and S2 on the bus coupler
The two rotary switches S1 and S2 for manual valve system address assignment are located
underneath the window (3).
Switch S1: The higher nibble of the last block of the IP address is set at switch S1. Switch S1
is labeled using the hexadecimal system from 0 to F.
Switch S2: The lower nibble of the last block of the IP is set on switch S2. Switch S2 is labeled
using the hexadecimal system from 0 to F.
The rotary switches are set to 0x00 by default. This activates address assignment via the "Browse
and Config" tool.
CAUTION
S1
S1
S2
S2