AVENTICS | Bus Coupler AES/Valve Driver AV, Ethernet POWERLINK | R412018143–BAL–001–AF

Structure of Pneumatic Supply Plate Data with UA-OFF Monitoring Board

8
Structure of Pneumatic Supply Plate Data
with UA-OFF Monitoring Board
The electrical UA-OFF monitoring board transfers all signals including the supply voltages.
The UA-OFF monitoring board recognizes whether the UA voltage falls below the UA-OFF value.
8.1

Process data

The electrical UA-OFF monitoring board does not have process data.
8.2

Diagnostic data

8.2.1

Cyclic diagnostic data o the UA-OFF monitoring board

The UA-OFF monitoring board sends the diagnostic message as a group diagnosis with the input
data to the bus coupler (see Table 14). The diagnostic bit for the corresponding module (module
number) indicates where the fault occurred. The diagnostic message consists of a diagnostic bit that
is set when the actuator voltage falls below UA-OFF.
The diagnostic bit can be read as follows:
Bit = 1: An error has occurred (UA < UA-OFF).
Bit = 0: No error has occurred (UA > UA-OFF).
8.2.2

Acyclic diagnostic data of the UA-OFF monitoring board via SDO

The diagnostic data of the UA-OFF monitoring board can be read out like the valve driver diagnostic
data (see section 6.2.2 "Acyclical diagnostic data of the valve drivers via SDO" on page 94).
8.3

Parameter data

The electrical UA-OFF monitoring board does not have parameters.