AVENTICS | Bus Coupler AES/Valve Driver AV, Ethernet POWERLINK | R412018143–BAL–001–AF

LED Diagnosis on the Bus Coupler

Reading the diagnostic
display on the bus coupler
UL
UA
IO/DIAG
S/E
L/A 1
L/A 2
11 LED Diagnosis on the Bus Coupler
The bus coupler monitors the power supplies for the electronic components and actuator control.
If they exceed or fall below a set threshold, an error signal will be generated and reported
to the controller. In addition, the status is displayed by the diagnostic LEDs.
The LEDs on the top of the bus coupler reflect the messages listed in Table 26.
Before commissioning and during operation, regularly check the bus coupler functions
by reading the LEDs.
Table 26:
Meaning of the diagnostic LEDs
14
Designation
Color
15
UL (14)
Green
16
Red
17
18
Red
Green/red
19
UA (15)
Green
Red
Red
IO/DIAG (16)
Green
Green/red
Red
Red
S/E (17)
Green
Green
Green
Green
Green
Red
Red
Green/red
L/A 1 (18)
Green
Green
Green
L/A 2 (19)
Green
Green
Green
State
Meaning
Illuminated
The electronics supply voltage is greater than the lower
tolerance limit (18 V DC).
Flashes
The electronics supply voltage is less than the lower
tolerance limit (18 V DC) and greater than 10 V DC.
Illuminated
The electronics supply voltage is less than 10 V DC.
Off
The electronics supply voltage is significantly less than
10 V DC (limit not defined).
Illuminated
Actuator voltage exceeds the lower tolerance limit
(21.6 V DC).
Flashes
The actuator voltage is less than the lower tolerance limit
(21.6 V DC) and greater than UA-OFF.
Illuminated
The actuator voltage is less than UA-OFF.
Illuminated
The configuration is OK and the backplane is working
perfectly.
Flashes
The module was not configured correctly in the controller
(too few cyclic objects were mapped to the PDOs).
Illuminated
Diagnostic message from module present.
Flashes
Valve unit incorrectly configured or backplane function
error
Illuminated
Module in the OPERATIONAL (RUN) status
Flashes
Simple Ethernet connection, no POWERLINK
quickly
communication
Flashes 1x
Module in PRE-OPERATIONAL-1 status
Flashes 2x
Module in PRE-OPERATIONAL-2 status
Flashes 3x
Module ready for OPERATIONAL (RUN) status
Illuminated
Communication error
Flashes
Communication aborted (module in STOP status)
Off
Initialization of the Ethernet system
Illuminated
The physical connection between the bus coupler and
network has been detected (link established).
Flashes
Data packets received (flashes for each data packet
quickly
received)
Off
The bus coupler does not have a physical connection with
the network.
Illuminated
The physical connection between the bus coupler
and network has been detected (link established).
Flashes
Data packets received (flashes for each data packet
quickly
received)
Off
The bus coupler does not have a physical connection with
the network.