Cable R meas
Determine cable resistance
p4109[0...5]
(with short-circuited sensor)
p4119[0...5]
p4108[0...5] = 0, 2, 3
Measuring
50/60 Hz
X53x.1
method
A
X53x.2
0: 1x2-concutcor
X53x.3
1: 2x2-conductor
D
X53x.4
2: 3-conductor
3: 4-conductor
x = 1, 2,
3, 4, 5, 6
p4121 (0)
Filt f_line
[9625]
<1> For p4102[0...23] = 251 °C the evaluation of the appropriate threshold is deactivated.
<2> p4100[0...11]
= 0: Evaluation disabled
= 1: PTC thermistor (with monitoring for short-circuit)
= 2: KTY84 (with monitoring for wire break and short-circuit)
= 4: Bimetal NC contact (no monitoring)
= 5: PT100 (with monitoring for wire break and short-circuit)
= 6: PT1000 (with monitoring for wire break and short-circuit)
<3> For p4103 = 0 s and sensor type "KTY84", "PT100", "PT1000" (p4100[0...11] = 2, 5, 6) the following applies:
- The relevant fault can only be triggered via the fault threshold (the timer output is always logical 0).
For p4103 = 0 s and sensor type "PTC thermistor", "Bimetal NC contact" (p4100[0...11] = 1, 4) the following applies:
- The corresponding alarm and fault are output simultaneously (delay time = 0 s).
<4> Only for 1x2-/2x2-conductor evaluation (p4108[0...5] = 0, 1).
1
2
DO: TM150
Terminal Module 150 (TM150) - Temperature evaluation 1x2-, 3-, 4-conductor (Channel 0 ... 5)
Save cable
Cable R value
resistance
p4110[0...5]
<4>
<4>
R
PT1000
Calculate
resistance
+
R
PT100
0
1
R
Temp filt T
KTY84
r4120
PTC/
Bimetal
NC
contact
Sensor R
r4101[0...5]
1650 Ÿ (PTC)
100 Ÿ (Bimetal)
3
4
Alarm threshold
-99...251 [°C]
p4102[0, 2, 4, 6, 8, 10] (251)
250 °C
T
-99 °C
Sensor type
250 °C
p4100[0...5]
<2>
T
PT1000
6
p4118[0...5] (5)
-99 °C
PT100
5
250 °C
Bimetal
4
KTY84
2
p4102[1, 3, 5, 7, 9, 11] (251)
T
PTC
1
0
-99 °C
-300 °C
1
0
1
0
250 °C
-50 °C
Temperature actual value
Alarm is present
-300 °C
5
6
fp_9626_51_eng.vsd
15.11.11 V04.05.00
"Channel y alarm is present"
<1>
0.0...600.0 [s]
r4104.0
A35211 (Channel 0)
p4103[0...5] (0.0)
r4104.2
A35212 (Channel 1)
<3>
1
r4104.4
A35213 (Channel 2)
T
0
r4104.6
A35214 (Channel 3)
0
r4104.8
A35410 (Channel 4)
r4104.10
A35411 (Channel 5)
"Channel y fault is present"
1
Fault threshold
-99...251 [°C]
r4104.1
F35207 (Channel 0)
r4104.3
F35208 (Channel 1)
<1>
r4104.5
F35209 (Channel 2)
1
r4104.7
F35210 (Channel 3)
r4104.9
F35400 (Channel 4)
only for
0
KTY84, PT100,
r4104.11
F35401 (Channel 5)
PT1000
A35920 ... A35925
"Error temperature sensor channel y"
(y = 0 ... 5)
0
Temp act value
r4105[0...5]
1
Group formation
7
Function diagram
SINAMICS
26000.00 μs
[9625.6]
8
- 9626 -