(X4)
Terminal of input neutral N.
(X5)
Terminal (copper bar) of main earth (
(X6)
Terminal of output phase U.
(X7)
Terminal of output phase V.
(X8)
Terminal of output phase W.
(X9)
Terminal of output neutral N.
(X10)
Terminal (copper rod) of earth bonding for for battery ca-
binet and / or loads connected directly to the UPS termi-
nals (
).
(X11) Battery positive terminal (+).
(4)
(X12) Battery negative terminal (–).
(4)
(X14)
Terminal of static bypass phase R (-B version only).
(X15)
Terminal of static bypass phase S (-B version only).
(X16)
Terminal of static bypass phase T (-B version only).
(X17)
Terminal of static bypass neutral N (-B version only).
(X23) Battery neutral N terminal (central tap).
(4)
(X31)
DB9 connector for COM 0 RS232/RS485 ports.
(X31
) USB connector for COM 0 ports.
USB
(X32)
DB9 connector for relay interface.
(X34)
Two terminal strip to connect the supplied 5 m. cable bundle,
which has at its opposite end a temperature probe. This probe
will be entered inside the battery cabinet in order to get the
floating voltage compensation according to its internal ambient
temperature.
(X34
) Ethernet connector, located in the BM630* electronic card and
ETH
installed in the UPS, which makes the function of a terminal
strip (X34) when the distance between cabinets (UPS and
batteries) exceeds 5 m. In this case, the Ethernet connection
(X38
) located in the optional BM655* electronic card and
ETH
fitted in the battery cabinet will be needed, in order to get the
voltage compensation according to the temperature.
(X36
)
HDB15 female connector, parallel bus input. Only useful in
i
parallel systems connection.
(X36
) HDB15 male connector, parallel bus output. Only useful in
o
parallel systems connection.
(X38
) Ethernet connector located in the optional BM655* electronic
ETH
card, which is fitted in the battery cabinet. It allows the digital
transmission from the collected information by the tempera-
ture probe fitted in the battery cabinet to the UPS, prior linking
both connectors (X34
ETH
(X45)
Two terminal strip, of the auxiliary contact of the output
switch. To be connected with its external counterpart fitted
in the manual bypass panel in parallel systems.
(X47)
Battery positive terminal (+) of the battery cabinet.
(X48)
Battery negative terminal (–) of the battery cabinet.
(X49)
Battery neutral terminal N of the battery cabinet (central
tap).
(X50)
External EPO terminals.
(X51)
Terminal strip of two terminals, auxiliary contact of manual by-
pass switch. To be connected to its external homologous.
Control panel (PC), keypad and optical indicators:
(LCD)
LCD panel.
(ENT)
Key «ENTER».
(ESC)
Key «ESC».
()
Key move up.
SALICRU
).
) and (X38
) with the cable.
ETH
()
Key move down.
()
Key move to right.
()
Key move to left.
(a)
Rectifier input voltage correct (green led).
(b)
Output voltage of the equipment from bypass (orange led).
(c)
Inverter ON (green led).
(d)
Output voltage from batteries -mains fault- (red led).
(e)
General alarm of the equipment, it is triggered with any
alarm (red led).
Other abbreviations:
(BC)
Communication BUS bundle between equipments, of 5 m.
length with HDB15 connectors in both ends.
(BF)
Rod to fix the connection wires of the equipment or battery
cabinet by means of wraps.
(BL)
Mechanical lock for manual bypass switch (Q5).
(CL)
Front door lock.
(LL)
Key to lock and unlock (CL).
(PB)
Levellers and fixing elements.
(PC)
Control panel.
(PF)
Front door.
(PR)
Cable gland or bushing to enter the cables.
(PT
)
Cable as a bridge mode, which closes the electrical circuit
1
between both pins of (X45), in case of lack of the auxiliary
contact.
(PT
)
Cable as a bridge mode, which closes the electrical circuit
2
between both pins of (X50), in case of lack of the EPO
button.
(R103) Two wires bundle with probe, to control the floating
voltage according to the temperature.
Equipments with separate battery cabinet only.
(RD)
Casters.
(RV)
Cooling grid.
(SL)
Slot for SICRES card (option).
(TB)
Terminal cover -connection elements-.
(t
)
Fixing screws for terminal cover (TB).
1
(t
)
Fixing screws for mechanical locking (BL) of switch (Q5).
2
Battery terminals (X11), (X12) and (X23) available in
(4)
models > 20 kVA (LV) / > 40 kVA (HV) only, or in equip-
ments B1 type (extended back up time).
By means of the connectors (X36
munication loop or ring is closed between two or more
equipments connected in parallel, by means of the bundle
(BC). These connectors are not useful when there is a
single equipment only.
Together with each UPS, it is supplied only one bundle (BC)
to connect the communication BUS. Therefore in any par-
allel system there will be the same quantity of communi-
cation bundles (BC) as equipments there are, so it makes
possible to close the communication loop.
Each communication bundle (BC) has 5 metres length and
it is provided with HDB15 connectors at both ends, one
male and another female.
) and (X36
) the com-
i
o
97