9. ANNEXES.
9.1.
PARTICULAR SPECIFICATIONS, EQUIPMENTS (LV).
Nominal power (kVA)
Nominal power (kW)
INPUT
Nominal voltage
Input voltage range
Frequency
Total input current distortion
(depending on the quality of input mains)
Current limit
Power factor
III/III (with common input)
III/III-B (rectifier input)
III/III-B (bypass input)
(L) I/I (with common input)
Rated conditional
(L) I/I-B (rectifier input)
short-circuit current
(L) I/I-B (bypass input)
-Icc- (kA)
(M) I/III-B (rectifier input)
(M) I/III-B (bypass input)
(N) III/I-B (rectifier input)
(N) III/I-B (bypass input)
INVERTER
Output nominal voltage
Output power factor
Accuracy
Output frequency
Maximum slew rate
Output wave shape
Total output voltage harmonic distortion
Phase shifting
Dynamic response time
Permissible overload
(7)
Permissible crest factor
Permissible power factor
Unbalanced output voltage (100 % unbalanced
Current limit
Efficiency on battery mode (100% linear load) (%)
STATIC BYPASS
Type
Bypass line
Nominal voltage
Voltage range
Voltage hysteresis
Frequency
Frequency range
Frequency hysteresis
Activation criteria
Transference time
Permissible overload
Transference to bypass
Re-transference
Efficiency on Smart ECO Mode (%)
MANUAL BYPASS (MAINTENANCE)
Type
142
5
7.5
10
15
Depending on the input/output setting and power supply voltage (See chart 9)
Single phase 115V, 120V, 127V or 133V
Three phase 3x200V, 3x208V, 3x220V or 3x230V (4 wires: 3 phases+ N)
50 / 60 Hz ±5 Hz ((selectable among 0.5 - 1 - 2 or 5 Hz)
100 % load: THD-i < 1.5 %
50 % load: THD-i < 2.5 %
10 % load: THD-i < 6.0 %
High overload: PFC limit (discharging batteries)
6
6
6
6
6
6
6
6
6
6
Single phase 115V, 120V, 127V or 133V
Three phase 3x200V, 3x208V, 3x220V or 3x230V (4 wires: 3 phases + N)
0.9 for three phase/three phase setting and 0.8 for L, M, N or AUTO settings
Static: ±1 %. Dynamic: ±2 % (step loads 100-0-100 %)
50 / 60 Hz synchronised ±5 Hz. Free running±0.05 %
Linear load: THD-v < 0.5 %. Ref. non-linear load (EN-62040-3): THD-v < 1.5 %
120 ±1º (balanced load). 120 ±2º (unbalanced load of 100 % )
125 % for 10 min., >125.. 135 % for 5 min., >135.. 150 % for 1 min., > 150 % for 20 ms.
3.4 to 1
High overload, short-circuit: RMS voltage limit. High current crest factor: Peak voltage limit
94.3
95.3
95.6
95.8
Single phase 115V, 120V, 127V or 133V
Three phase 3x200V, 3x208V, 3x220V or 3x230V (4 wires: 3 phases + N)
Preset +12 % (adjustable between +20... +5%) / –15% (adjustable between –25... –5%
±2 % as regards the bypass voltage range. In a standard equipment is +10 /–13%
±5 Hz (selectable between 0.5 - 1.0 - 2 and 5.0 Hz)
1 Hz as regards the frequency range (selectable among 0.2 - 0.5 - 1.0 and 2.0 Hz)
Immediately, for overloads over 150 %
95.0
95.5
96.0
97.4
20
30
40
+15% / –20% (configurable)
100 % load: THD-i < 1.0 %
50 % load: THD-i < 2.0 %
10 % load: THD-i < 5.0 %
1.0 from 10% load
10
-
10
-
10
-
10
-
10
-
10
-
10
-
From 1 to 10 Hz/s (programmable)
Sinewave
10 ms. till 98 % of the static value
3.2 to 1
2.8 to 1
0.7 leading to 0.7 lagging
< 1 %
96.4
Solid state(SCR)
Common. Separate as an option (B)
50 / 60 Hz
Controlled by microprocessor
Nil, less in Smart ECO Mode < 4 ms
400 % for 10 s
Automatic after alarm cancelling
97.8
98.0
98.4
Make before break
50
60
80
100
-
100 % load: THD-i < 1.5 %
50 % load: THD-i < 2.0 %
10 % load: THD-i < 6.0 %
10
10
10
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3.2 to 1
3 to 1
96.5
96.4
96.8
96.9
-
98.0
USER MANUAL