8. MAINTENANCE, WARRANTY AND SERVICE.
8.1.
MAINTENANCE BASIC GUIDE.
Batteries, fans and capacitors must be replaced at the end of their
useful lifetime.
Inside the UPS there are dangerous voltages and metallic
parts at very high temperatures, although the UPS is shut-
down. The direct contact can cause electrocutions and burns. All
the operating, less the battery fuse replacing, must be done by au-
thorised technical staff.
Some internal parts of the UPS (terminals, EMC filters and
measurement circuits) are still under voltage during the
maintenance bypass operating. To cancel all the voltages, the cir-
cuit breakers of mains and bypass of the panel board that feeds the
UPS and the fuse holders of the battery rack have to be turned
«OFF» / «0».
8.1.1.
Battery fuses.
Turning on the battery switch and/or fuse holder «ON» or «I» posi-
tion, and only after displaying the alarm message «BATT. SWITCH
OPEN, SWITCH IT ON» in the LCD panel.
The battery fuses can only be replaced by ultrafast fuse
models type aR 660V, of the same size and current used in
the equipment and/or battery module.
8.1.2.
Batteries.
The useful lifetime of the batteries depends on the ambient temper-
ature and other factors like the quantity of charging and discharging
cycles and the deep discharges done.
Its design lifetime is between 3 and 5 years if the ambient tempera-
ture is between 10 and 20 ºC. Under request, other typology and/or
design lifetime batteries can be supplied.
To get more information about their status, activate the battery
test.
Risk of fire and/or explosion exists if a wrong quantity or type
of batteries is used. Do not dispose the batteries to the fire:
they can explode. Do not open and mutilate the batteries: the
dumped electrolyte is dangerous for the skin and eyes. It can be
toxic.
8.1.3.
Fans.
The useful lifetime of the used fans to cool the power circuits de-
pends on the use and environment conditions. It is recommended
their preventive replacement by authorised technical staff.
SALICRU
8.1.4.
Capacitors.
The useful lifetime of the DC bus capacitors and those ones used in
the input and output filtering depends on the use and the environ-
ment conditions. It is recommended their preventive replacement
by authorised technical staff.
8.2.
WARRANTY CONDITIONS.
8.2.1.
Warranty terms.
The warranty conditions for the acquired product can be found in
our website and in that you will be able to register it. It is recom-
mended to do it as soon as possible in order to include it in the
Technical Service & Support (T.S.S.) database. Among other ad-
vantages, it will be easier to make any regulatory process to allow
the (T.S.S.) action in case of any hypothetical fault.
8.2.2.
Out of scope of supply.
Our company is not forced by the warranty if it appreciates that
the defect in the product doesn't exist or it was caused by a wrong
use, negligence, installation and/or inadequate testing, tentative of
non-authorised repairing or modification, or any other cause beyond
the foreseen use, or by accident, fire, lightnings or other dangers.
Neither it will cover, in any case, compensations for damages or
injuries.
8.3.
TECHNICAL SERVICE NETWORK.
Coverage, both national and international, from our Technical Ser-
vice & Support (T.S.S.), can be found in our Website.