Fig. 39. Battery configuration label affixed to the equipment.
• In equipments with touchscreen, the installation menu will be
displayed by means of 2 screens with all the parameters to select.
Proceed according to section 1 of the EL064*01 document.
English
7
12
0
2022
February
Monday
Fig. 40. First configuration screen.
If Spanish has been chosen on the language screen, this will
be the default language that will appear on the rest of the
screens. For the rest of the languages, the screen will appear in
English by default until it is changed in the First configuration screen
(Fig. 40).
1
Fig. 41. Second HV equipment configuration screen.
SALICRU
In the case of LV equipment, this second screen changes:
3x400 V
50 Hz
Fig. 42. Second LV equipment configuration screen.
6.2.2.2. Daily start up procedure, for equipments with
When coming from the previous section the first three steps will be
skipped, because they are already done in the first commissioning.
For the daily start up procedure, starting from equipment/s shutdown
completely, make all the next stated actions:
• Supply input voltage to the switchgear panel board.
• Turn «On» the input switch or switches of the panel board, de-
• Turn the UPS or each UPS input switch (Q1a) to «On» position.
• The LCD of the Control Panel (PC) of each equipment will be
70 Ah
1
36 (18+18)
alphanumerical display.
pending if it is a single equipment or parallel system.
turned on automatically.
For single equipments the LCD panel will display the left mes-
sage of the screen 0.0 and for parallel systems both messages
will be displayed 0.0 :
Ì
SLC CUBE 3+
É
11:19:35 11/09/2013
screen 0.0
70 Ah
Paral. 002 Out. SW=OFF
11:19:35 11/09/2013
screen 0.0
119