4 Operating the Power System
Step 5. Specify if you want the list to generate trigger signals that can be used to trigger actions on
other output channels or on external equipment connected to the digital port.
Front Panel Menu Reference
Select Transient\List\Config.
Select the List Step number.
To generate a trigger, enter a 1 in the Tout begin step or
Tout end step field. If a zero is entered, no trigger is
generated for the step.
Repeat this for each step. Use the
the next step.
Step 6. Specify how you want the list to terminate. For example, if you want the list to remain at the
values of the last list step when finished, use:
Front Panel Menu Reference
Select Transient\List\Terminate.
Select Stop at last step settings. Then press Select.
Step 7. If applicable, specify how many times you want the list to repeat. Sending the INFinity
parameter in the SCPI command makes the list repeat indefinitely. At reset, the list count is set to 1.
Front Panel Menu Reference
Select Transient\List\Repeat.
Enter the number of List repetitions (2). Then press
Select.
Step 8. Select a trigger source, then initiate, and trigger the list. This is previously described under
Program an Output Pulse or Pulse
116
To program a trigger at the start of step 4 for output 1,
use
LIST:TOUT:BOST 0,0,0,0,1,0,@(1)
To program a trigger at the end of step 0, 2, and 4 for
output 1, use
LIST:TOUT:EOST 1,0,1,0,1,0,(@1)
ÇÈ
keys to select
To program output 1, use
LIST:TERM:LAST 1,(@1)
To program the output 1 list to repeat 2 times, use
LIST:COUN 2,(@1)
Train.
SCPI Command
SCPI Command
SCPI Command
Keysight N6700C Series User's Guide