Front Panel Menu Reference
Select System\Preferences\Display\Saver
Enable or disable the screen saver by checking or unchecking the Screen
Saver checkbox. Then press Select.
Enter a value in minutes in the Saver Delay field to specify the time when
the screen saver will activate.
Check Wake on I/O to activate the display with I/O bus activity.
Front Panel Keys
Lockout
You can lock the front panel keys to prevent unwanted control of the instrument from the front panel.
This is the most secure way of locking the front panel keys because you need a password to unlock the
front panel. The lockout setting is saved in non-volatile memory so that the front panel remains locked
even after AC power is cycled.
Front Panel Menu Reference
Select System\Preferences\Lock
Enter the password to unlock the front panel. Then
select Lock.
The menu to unlock the front panel appears every time a
key is pressed. Enter the password to unlock the front
panel.
If the password is lost, the SYSTem:PASSword:FPANel:RESet command can reset the
front panel lockout password.
The SYSTem:COMMunicate:RLSTate RWLock command can also lock and unlock the
front panel. This command is completely independent of the front panel lockout
function. If you use this command to lock the front panel, the front panel will be
unlocked when AC power is cycled.
Keys
You can enable or disable the front panel key clicks.
Front Panel Menu Reference
Select System\Preferences\Keys
Check Enable key clicks to enable key clicks. Press
Select.
Uncheck to disable key clicks.
You can configure the On/Off key to enable or disable ALL outputs.
Keysight N6700C Series User's Guide
4 Operating the Power System
SCPI Command
Not available
SCPI Command
Not available
SCPI Command
Not available