Model 100199
TROUBLESHOOTING
NO AC OUTPUT
1.
HSB set in "TEST" mode
2.
Circuit breaker in "OFF" position
3.
ATS control in "OFF" mode
4.
Main circuit breaker in "OFF" position.
5.
Transfer switch breaker in "OFF" position.
6.
Standby breakers set in "OFF" position.
7.
Line circuit tripping breaker because of short circuit *
8.
Line circuit tripping breaker because of overload *
9.
Poor wiring connections*
10. ATS problems*
LED INDICATORS
In all cases when the LED is GREEN, this is an indicator that the HSB is performing properly.
In all cases when the LED is RED, this is an indicator that the HSB has registered a fault and must be corrected. Only the "LOW BATTERY
LED" will not latch out or shut down the HSB. All other RED LED faults will latch out, shut down, disable starting and light the RED LEDS on
the Engine Control Module and the exterior fault code light on the backside of the HSB.
RESET FAULT CODE(S)
There is an exterior fault code indicator light located on the back of the enclosure. This should be checked weekly to make sure there are
no active fault codes.
The fault code(s) can be reset by placing the Engine Control Module in the OFF position for 10 seconds and then placed into ATS mode.
This will reset fault LED, however if a fault code(s) re-occurs it must be addressed.
BATTERY(S) NO OR LOW LEVEL CHARGED, BATTERY(S) DEAD, NEEDS REPLACEMENT, THE EXERCISE TIME MUST BE RESET
ONCE THE BATTERY(S) HAVE BEEN DISCONNECTED.
*Contact Champion Power Equipment, Technical Service toll free 1-877-338-0999,
tech@championpowerequipment.com or your nearest Champion dealer.
www.championpowerequipment.com
52
Part No. 101049 Rev. B
Place HSB in AUTO and ATS mode.
Turn on breaker.
Place ATS module in ATS mode.
Turn on breaker.
Turn on breaker.
Turn on breaker.