INSTALLATION
LED INDICATORS
In all cases when the LED is GREEN, this is an indicator that the
HSB is performing properly.
In all cases when the LED is RED, this is an indicator that the
HSB has registered a fault and must be corrected. Only the "LOW
BATTERY LED" will not latch out or shut down the HSB. ALL other
RED LED faults will latch out, shut down, disable starting and
light the RED LEDs on the Engine Control Module and the exterior
fault code LED on the backside of the HSB.
APPROXMATE ENGINE STARTER CRANK CYCLE TIMES
10 seconds ON
10 seconds OFF
10 seconds ON
10 seconds OFF
10 seconds ON
10 seconds OFF
10 seconds ON
10 seconds OFF
10 seconds ON
If the HSB fails to start, the "OVER CRANK LED will be lit on the
Engine Control module and the exterior fault code indicator LED
on the backside of the HSB.

PIN LOCATIONS

(ON BACKSIDE OF THE CONTROLLER)
The pins relate to a function of the Engine Controller module.
These functions control the operation of the HSB and ATS. The
ECM continually monitors the Utility source power 24/7. There
only 14 pin locations. Remember the LEDs on the front side of
the module are only indicators of a run (GREEN) or fault (Red).
These are the designated pin locations, function and wire colors
for reference;
1.
Pin 1
B+
38
Part No. 101049 Rev. B
W(White)
2.
Pin 2
B-
3.
Pin 3
Motor start signal
4.
Pin 4
Fuel valve
5.
Pin 5
Drives all fault lights
6.
Pin 6
Ground/stop
7.
Pin 7
Signal to alternator
8.
Pin 8
Not Connected
9.
Pin 9
Low Oil Level/
Pressure
10. Pin 10
Engine High Temp
11. Pin 11
Exercise
12. Pin 12
Signal to ATS
13. Pin 13
Frequency Over/
Under
14. Pin 14
Frequency Over/
Under
DIP SWITCHES ON THE BACK SIDE OF THE CONTROL IN
BETWEEN THE 2 ROWS OF PIN CONNECTORS
The Dip Switches assist the ECM by setting parameters of control
such as delays of time or intervals for signals. There are only 10
dip switches. These are the designated "ON" or "OFF" position
settings for the dip switches (factory pre-set);
1.
1 – 7 are all in the "OFF" position
2.
8 is the only dip switch in the "ON" position
3.
9 – 10 are in the "OFF" position

ATS CONTROL MODULE

The ATS Control Module contains the TEST/AUTO/OFF switch
and LEDs that indicate the type/source of power delivery into
the home. The module will reflect Utility power source when the
utility power source is coming into the home. The 3 LEDs on the
left will be lit (UTILITY, ATS active, LOAD, view left to right).
The module will reflect GENSET power when the Generator is
the source of power being delivered into the home. The 3 LEDs
on the right will be lit (LOAD, ATS active, GENSET, view center to
right).
This is a two (2) wire start system. The control of HSB operation
and ATS operation are done through the controls in the HSB.
This is done by a wire connection to the HSB and then a wire
correction from the HSB to the ATS. All system communications,
G (Green)
B/W (Black/White)
G/B (Green/Black)
L (Blue)
L/B (Blue/Black)
R/B (Red/Black)
Y (Yellow)
Br (Brown)
O/B (Orange/Black)
O (Orange)
B (Black)
R (Red)